Detailed Control Functions
SiBE341001
57
Function
2.7.5 Cooling/heating mode changeover
[Single room cooling under mixed cooling and heating conditions
→
heating]
First, close all of the indoor unit electronic expansion valve and BS unit electronic expansion valves Y2E, Y3E, Y4E and
Y5E under the cooling operation condition.
Next, open the electronic expansion valve Y2E and perform an equalizing operation. Subsequently, both the electronic
expansion valve Y4E and the indoor unit electronic expansion valve open to become a heating circuit. The changeover
time is about 6 minutes. (However, this can be shortened from 6 minutes to 4 minutes depending on the onsite setting.)
(1) Cooling operation
(2) Pressure equalizing
(3) Heating operation
Y4E
Y5E
Y3E
Y2E
Y1E
Liquid pipe
HP / LP gas pipe
Suction gas pipe
Indoor Unit
Cooling
Unit
BS Unit
Y4E (Close)
Y5E (Close)
Y2E (Open)
Y3E (Close)
Y1E
(Close)
Liquid pipe
HP / LP gas pipe
Suction gas pipe
Indoor Unit
BS Unit
Y4E
Y5E
Y2E
Y3E
Y1E
Liquid pipe
HP / LP gas pipe
Suction gas pipe
Indoor Unit
Heating
Unit
BS Unit
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...