Detailed Control Functions
Function
58
[Single room heating under mixed cooling and heating conditions
→
cooling]
First, close all of the indoor unit electronic expansion and BS unit electronic expansion valves Y2E, Y3E, Y4E and Y5E
under the heating operation condition.
Next, open the electronic expansion valve Y3E and perform an equalizing operation. Subsequently, the electronic
expansion valve Y5E opens and the indoor unit electronic expansion valve adjusts the opening extent to become a
cooling circuit. The changeover time is about 6 minutes. (However, this can be shortened from 6 minutes to 4 minutes
depending on the onsite setting.)
(1) Heating operation
(2) Pressure equalizing
(3) Cooling operation
Y4E
Y5E
Y2E
Y3E
Y1E
Liquid pipe
HP / LP gas pipe
Suction gas pipe
Indoor Unit
Heating
Unit
BS Unit
Y4E (Close)
Y5E (Close)
Y2E (Close)
Y3E (Open)
Y1E
(Close)
Liquid pipe
HP / LP gas pipe
Suction gas pipe
Indoor Unit
BS Unit
Pressure
equalizing
Y4E
Y5E
Y3E
Y2E
Y1E
Liquid pipe
HP / LP gas pipe
Suction gas pipe
Indoor Unit
Cooling
Unit
BS Unit
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...