Field Setting from Outdoor Unit
SiBE341001
69
Test Operation
2. Field Setting from Outdoor Unit
2.1
Field Setting from Outdoor Unit
2.1.1 List of Field Setting Items
This following section indicates the list of field setting items. For the lists of dip switch contents,
Setting mode 1, and Setting mode 2, refer to information in tables shown on the following page
onward.
For setting items of (*1), refer to detailed information provided on page 80 onward.
(1) Function setting items
Setting item
Content and objective of setting
Overview of setting procedure
1
Setting of COOL/
HEAT selection (*1)
COOL/HEAT selection methods are
possible to select from the following
(1) Control by each outdoor unit using the
indoor unit remote controller
(2) Control by each outdoor unit using the
COOL/HEAT selection remote controller
(3) Batch control by outdoor unit group using
the indoor unit remote controller
(4) Batch control by outdoor unit group using
the COOL/HEAT selector remote
controller
In order to use the COOL/HEAT selection
remote controller, set the DS1-1 on the outdoor
unit PCB to OUT.
For outdoor unit group control, set the system
to "BATCH MASTER" or "SLAVE" while in
"Setting mode 1". Then, make setting of COOL/
HEAT batch address.
2
Setting of low noise
operation (*1)
A. Use external input to step down the upper
limit of the fan (factory set to Step 8),
providing low noise level.
(1) Mode 1: Step 6 or lower
(2) Mode 2: Step 5 or lower
(3) Mode 3: Step 4 or lower
Use the "External control adaptor for outdoor
unit".
Set to "External control adaptor for outdoor
unit" with No. 12 of "Setting mode 2" and select
the mode with No. 25.
If necessary, set the "Capacity precedence
setting" to ON with No. 29.
B. The low noise operation aforementioned is
enabled in night-time automatic low noise
operation mode.
Start time: Possible to select in the range of
20:00 to 24:00 hours.
End time: Possible to select in the range of
06:00 to 08:00 hours.
(Use the said time as a guide since the start
time and the end time are estimated
according to outdoor temperatures.)
Make this setting while in "Setting mode 2".
Select a mode with No. 22 of "Setting mode 2".
Select the start time with No. 26 and the end
time with No. 27.
If necessary, set the "Capacity precedence
setting" to ON with No. 29.
3
Setting of demand
operation (*1)
Used to place limits on the compressor
operating frequency to control the upper limit
of power consumption.
(1) Mode 1 of Demand 1: 60% or less of
rating
(2) Mode 2 of Demand 1: 70% or less of
rating
(3) Mode 3 of Demand 1: 80% or less of
rating
(4) Demand 2: 40% or less of rating
(5) Demand 3: Forced thermostat OFF
Method using the external control adaptor for
outdoor unit.
Select Demand 1 – 3 by short-circuit the
terminal strip (TeS1).
Setting by "Setting mode 2" only
Select Demand 1 or Demand 2 using set No.
32 of "Setting mode 2". If Demand 1 is selected,
then also select Level 1 – 3 using set No. 30.
4
Setting of AIRNET
address
Used to make address setting with AIRNET
connected.
Set the AIRNET to an intended address using
binary numbers with No. 13 of "Setting mode
2".
5
Setting of high
static pressure
Make this setting to operate a system with
discharge duct while in high static pressure
mode. (Use this setting mode when
concealed outdoor unit installation is
required on upper floors or balconies.)
* In order to mount the discharge duct,
remove the cover from the outdoor unit fan.
Set No. 18 of "Setting mode 2" to ON.
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...