Field Wiring
SiE33-003
156
Installation Manual
7.6.7
Sequential Start
Make the outdoor unit cable connections shown below.
The outdoor unit PC board (A1P) is factory set at “Sequential start available”.
7.6.8
Setting the Cool/Heat Operation
1. Performing cool/heat setting with the remote control connected to the indoor unit.
Keep the cool/heat selector switch (SS1) on the outdoor unit PC board (A1P) at the factory setting
position IN/D UNIT.
2. Performing cool/heat setting with the cool/heat selector.
Connect the cool/heat selector remote control (optional) to the A/B/C terminals and set the cool/heat
selector switch (SS1) on the outdoor unit PC board (A1P) to OUT/D UNIT.
Caution
For low-noise operation, it is necessary to get the optional “External control adaptor for outdoor unit”.
For details, see the installation manual attached to the adaptor or service manual Si33-002.
1. Indoor unit
A B C F1
F1
F2
F2
A B C F1
F1
F2
F2
A1P
A1P
1
1
Fig. 24
(V0876)
1. Remote control
1.Cool/Heat selector
TO IN/D
UNIT
F1 F2
IN/D
UNIT
OUT/D
UNIT
SS1
C/H
SELECT
F1 F2
F1 F2
F1 F2
1
Fig. 25
(V0877)
IN/D
UNIT
OUT/D
UNIT
SS1
C/H
SELECT
A B C
A B C
1
Fig. 26
(V0878)