Installation
SiE33-003
42
General Information
2. After piping work is finished, check drainage flows smoothly.
Open the water inlet lid, add approximately 600 cc of water slowly and check drainage flow.
WHEN ELECTRIC WIRING WORK IS FINISHED
Check drainage flow during COOL running, explained under “TEST OPERATION”.
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
Remove the electric parts box lid, connect a power supply and remote control to the terminals.
Next, press the inspection/test operation button “
” on the remote control. The unit will engage the
test operation mode. Press the operation mode selector button “
” until selecting FAN
OPERATION “
”. Then, press the ON/OFF button “
”. The indoor unit fan and drain pump will
start up. Check that the water has drained from the unit. Press “
” to go back to the first mode.
Note that the fan also starts rotating.
FXYKP-ceiling
mounted corner
cassette
1. Install the drain pipes.
Keep piping as short as possible and slope it downwards so that air may not remained trapped inside
the pipe.
Keep pie size equal to or greater than that of the connecting pipe (Vinyl pipe of 25 mm nominal diam.
and 32 mm outer diam.).
Use the attached drain hose and clamp. Tighten the clamp firmly.
Insulate the clamp with the attached sealing pad.
[Method of adding water]
Switch box
cover (1)
Switch box
cover (2)
Terminal board for
remote control (6P)
Lead cable for remote control
Power supply
Power supply
terminal board (2P)
3PA60996-10L
L
N
P1 P2 F1 F2 T1 T2
Si33-003.book Page 42 Monday, June 25, 2001 9:06 AM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html