SiE33-003
Installation
General Information
49
The table below indicates our recommendations as to the appropriate spacing of control and power
cables where these are to be run side by side.
Notes:
1. The figures are based on an assumed length of parallel cabling up to 100m. For lengths in excess of
100m the figures will have to be recalculated in direct proportion to the additional length of cable
involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
If the cables are laid inside conduits then the following points must also be taken into account when
grouping various cables together for introduction into the conduits.
1. Power cables (including power supply to the air conditioner) and signal cables must not be laid inside
the same conduit. (Power cables and signal cables must each have their own individual conduits.)
2. In the same way, when grouping the cables, power and signal cables should not be bunched together.
Important points
1. Earthing
Have the indoor and outdoor units both been earthed?
∗
If the apparatus is not properly earthed then there is always a risk of electric shocks. The earthing of the
apparatus must be carried out by a qualified person.
Current capacity of power cable
Spacing (d)
100V or more
10A or less
300mm
50A
500mm
100A
1000mm
100A or more
1500mm