Wiring

WARNING

•  Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.
• 

Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• 

Be sure to install a ground fault circuit interrupter. (One that can handle higher harmonics.)  
(This unit uses an inverter. Therefore, a ground fault circuit interrupter capable of handling higher harmonics must be used in 
order to prevent the ground fault circuit interrupter malfunctioning.)

• 

Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.

• 

When carrying out wiring, take care not to pull at the conduit.

•  Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• 

Do not turn on the circuit breaker until all work is completed.

1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the 

terminal screws securely. It is recommended that a flathead screwdriver be used to tighten the screws. 

 

The screws are packed with the terminal block.

1

2

3

1 2 3

Circuit 

breaker

Ground fault

circuit interrupter

Ground

Firmly fix the wires with 
the te

r

minal screws.

Use AWG16 if the connection wire
length is less than 33ft (10m), or
AWG14 if it is 33ft (10m) or more.

Outdoor unit

Indoor 
unit

Power supply
60Hz 208-230V

Firmly fix the 
wires with the 

ter

minal screws.

Use AWG 14 wires.

RX09/12

, RK09/12

RXN09/12/18

, RKN09/12/18

, RXL09/12/15

RX18/24

, RK18/24

RXN24

, RKN24

15A

20A

L

1

 

L

2

09/12 class

[Method of mounting conduit]

•  A protection plate is fixed for protection from the high-voltage section.

1) Dismount the stop valve cover by removing the screw.
2) Dismount the protection plate by removing the 2 screws.
3) Dismount the conduit mounting cover by removing the 2 screws.
4) Pass wires through the conduit and secure them with a lock nut.
5) After completing the work, reattach the stop valve cover, the conduit mounting cover, and the protection plate to its 

original position.

1

2

3

1

2

3

1

2

3

Screws

Conduit
mounting
cover

Screws

Protection plate

Power supply
terminal block

Shape wires so 
that the protection 
plate and conduit 

mounting plate fit 

securely.

Conduit

Lock nut

Conduit 
mounting 
plate

L

1

L

2

01_EN_3P379970-6B.indd   9

11/13/2015   15:48:27

Summary of Contents for RX09NMVJU

Page 1: ...U RXN18NMVJU RXN24NMVJU RK09NMVJU RK12NMVJU RK18NMVJU RK24NMVJU RKN09NMVJU RKN12NMVJU RKN18NMVJU RKN24NMVJU RXL09QMVJU RXL12QMVJU RXL15QMVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split...

Page 2: ...ts and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe s...

Page 3: ...re should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet ra...

Page 4: ...re more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditio...

Page 5: ...length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 1...

Page 6: ...w Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15 16 100 More than 13 3 4 350 More than 1 15 16 50 W...

Page 7: ...in order to guarantee its service life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut f...

Page 8: ...e than 550psi 3 8MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose t...

Page 9: ...on materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kca...

Page 10: ...Tighten the terminal screws securely It is recommended that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 Circuit breaker Ground fault...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...Pump Down Operation In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out f...

Page 13: ...the instructions in the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation...

Page 14: ...Two dimensional bar code is a manufacturing code 3P379970 6B M15B135 1511 HT...

Reviews: