background image

10

English

15/18/24 class

[Method of mounting conduit]

1) Dismount the service lid by removing the 2 screws.
2) Pass wires through the conduit and secure them with a lock nut.
3) After completing the work, reattach the service lid to its original position.

1

2

3

1

2

3

Power supply
terminal block

Shape wires so 
that the protection 
plate and conduit 

mounting plate fit 

securely.

Service lid

Screws

Conduit

Lock nut

Conduit mounting plate

L

1

L

2

CAUTION

Precautions to be taken for power supply wiring

• 

When using stranded wires, make sure to use the round crimp-style 
 terminal for connection to the power supply terminal block.

Stranded wire

Round crimp-style
terminal

Arrow view 

Flat washer

Screw

Round 

crimp-style 

terminal

Good

Round crimp-
style terminal

Flat washer

Screw

Wrong

Flat washer

Round crimp-
style terminal

Screw

A

A

• 

When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead. 

 Improper work may cause heat and fires.

Strip wire end
to this point.

Excessive strip length

may cause electric shock 

or current leakage.

Stripping wire at terminal block

Good

Wrong

Good

Wrong

English

01_EN_3P379970-6B.indd   10

11/13/2015   15:48:27

Summary of Contents for RX09NMVJU

Page 1: ...U RXN18NMVJU RXN24NMVJU RK09NMVJU RK12NMVJU RK18NMVJU RK24NMVJU RKN09NMVJU RKN12NMVJU RKN18NMVJU RKN24NMVJU RXL09QMVJU RXL12QMVJU RXL15QMVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split...

Page 2: ...ts and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe s...

Page 3: ...re should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet ra...

Page 4: ...re more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditio...

Page 5: ...length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 1...

Page 6: ...w Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15 16 100 More than 13 3 4 350 More than 1 15 16 50 W...

Page 7: ...in order to guarantee its service life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut f...

Page 8: ...e than 550psi 3 8MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose t...

Page 9: ...on materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kca...

Page 10: ...Tighten the terminal screws securely It is recommended that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 Circuit breaker Ground fault...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...Pump Down Operation In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out f...

Page 13: ...the instructions in the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation...

Page 14: ...Two dimensional bar code is a manufacturing code 3P379970 6B M15B135 1511 HT...

Reviews: