8

English

6. 

Refilling refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A
Fill from the liquid pipe in liquid form.

R410A is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal 
operation.
1) 

Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

Filling a cylinder with an attached siphon

Stand the cylinder upright when filling.

There is a siphon pipe inside, so the cylinder 

need not be upside-down to fill with liquid.

Filling other cylinders

Turn the cylinder 

upside-down when filling.

• 

Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

7. 

Refrigerant piping work 

7-1. Cautions on pipe handling

• 

Protect the open end of the pipe from dust and moisture.

• 

All pipe bends should be as gentle as possible. Use a pipe bender for 
bending.

7-2. Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

• 

Insulation material: Polyethylene foam

 Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 
to 0.045kcal/mh°C))

Be sure to use insulation that is designed for use with HVAC Systems.

• 

ACR Copper only.

• 

Be sure to insulate both the gas and liquid piping and observe the 
insulation dimensions as below.

Wall

If no flare cap is 

available, cover 

the flare mouth 

with tape to keep 

dirt and water out.

Be sure to 

place a cap.

Rain

Gas side

Piping size

O.D. 3/8 inch

(9.5mm)

O.D. 1/2 inch

(12.7mm)

O.D. 5/8 inch

(15.9mm)

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm)

or more

1-9/16 inch (40mm)

or more

1-15/16 inch (50mm)

or more

1-3/16 inch (30mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

0.039 inch (1.0mm)

(C1220T-O)

0.031 inch (0.8mm)

(C1220T-O)

I.D. 15/32-19/32 inch

(12-15mm)

I.D. 9/16-5/8 inch

(14-16mm)

I.D. 5/8-13/16 inch

(16-20mm)

I.D. 5/16-13/32 inch

(8-10mm)

13/32 inch

(10mm) Min.

Minimum bend radius

Piping thickness

Thermal insulation size

Thermal insulation

thickness

Liquid side

• 

Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wire

English

01_EN_3P379970-6B.indd   8

11/13/2015   15:48:26

Summary of Contents for RX09NMVJU

Page 1: ...U RXN18NMVJU RXN24NMVJU RK09NMVJU RK12NMVJU RK18NMVJU RK24NMVJU RKN09NMVJU RKN12NMVJU RKN18NMVJU RKN24NMVJU RXL09QMVJU RXL12QMVJU RXL15QMVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split...

Page 2: ...ts and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe s...

Page 3: ...re should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet ra...

Page 4: ...re more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditio...

Page 5: ...length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 1...

Page 6: ...w Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15 16 100 More than 13 3 4 350 More than 1 15 16 50 W...

Page 7: ...in order to guarantee its service life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut f...

Page 8: ...e than 550psi 3 8MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose t...

Page 9: ...on materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kca...

Page 10: ...Tighten the terminal screws securely It is recommended that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 Circuit breaker Ground fault...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...Pump Down Operation In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out f...

Page 13: ...the instructions in the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation...

Page 14: ...Two dimensional bar code is a manufacturing code 3P379970 6B M15B135 1511 HT...

Reviews: