Main Functions
Part 4 Functions and Control
33
Note(s)
2. Motions (in cooling)
In FAN operation, the fan speed is reduced by 60 rpm when no one is in the area.
When there is no signal from the motion sensor in 20 minutes, the microcomputer judges that
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling/Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time)
3. Airflow direction in 2-area INTELLIGENT EYE operation
Detection method: The opposite area of detected area is set as the target direction.
1. Human detection signal ON in both areas A and B: Shift the airflow direction to area B (left side)
2. Human detection signal ON in area A: Shift the airflow direction to area B (left side)
3. Human detection signal ON in area B: Shift the airflow direction to area A (right side)
4. Human detection signal OFF in both areas A and B: No change
When the human detection signal is OFF for 20 minutes in both areas A and B, the unit starts
energy saving operation.
For dry operation, the temperature cannot be set with a remote controller, but the target
temperature is shifted internally.
ON
OFF
Reset
Reset
Reset
20 min.
1 ~ 2°C (1.8 ~ 3.6 °F)
ON
OFF
ON
OFF
Operation
OFF
Fan speed (
#
)
Set speed
Set speed
Target temperat
u
re
(R23920)
Remote controller
Sensor
b
u
tton
H
u
man detection
signal
↑
↑
60 rpm
↑
within
20 min.
within
20 min.
within
20 min.
Top view
Wall
Indoor
u
nit
Area A
Area B
Left
Right
H
u
man
(R3853)
Summary of Contents for RX09RMVJU9
Page 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications ...
Page 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1 ...
Page 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E ...