Control Specification
Part 4 Functions and Control
47
D signal for cooling
OFF = Thermostat OFF
D signal for heating
OFF = Thermostat OFF
PI Control
1.
P control
The
D value is calculated in each sampling time (20 seconds), and the frequency is adjusted
according to its difference from the frequency previously calculated.
2.
I control
If the operating frequency does not change for more than a certain fixed time, the frequency is
adjusted according to the
D value.
When
D value is low, the frequency is lowered.
When
D value is high, the frequency is increased.
3.
Frequency control when other controls are functioning
When frequency is dropping:
Frequency control is carried out only when the frequency drops.
For limiting lower limit:
Frequency control is carried out only when the frequency rises.
4.
Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set according to the command of the indoor unit.
When the indoor or outdoor unit quiet operation command comes from the indoor unit, the upper
limit frequency is lower than the usual setting.
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–2.0°C (–3.6°F)
OFF
0°C (0°F)
4
2.0°C (3.6°F)
8
4.0°C (7.2°F)
12
–1.5°C (–2.7°F)
1
0.5°C (0.9°F)
5
2.5°C (4.5°F)
9
4.5°C (8.1°F)
13
–1.0°C (–1.8°F)
2
1.0°C (1.8°F)
6
3.0°C (5.4°F)
10
5.0°C (9.0°F)
14
–0.5°C (–0.9°F)
3
1.5°C (2.7°F)
7
3.5°C (6.3°F)
11
5.5°C (9.9°F)
15
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–1.5°C (–2.7°F)
OFF
0.5°C (0.9°F)
4
2.5°C (4.5°F)
8
4.5°C (8.1°F)
12
–1.0°C (–1.8°F)
1
1.0°C (1.8°F)
5
3.0°C (5.4°F)
9
5.0°C (9.0°F)
13
–0.5°C (–0.9°F)
2
1.5°C (2.7°F)
6
3.5°C (6.3°F)
10
5.5°C (9.9°F)
14
0°C (0°F)
3
2.0°C (3.6°F)
7
4.0°C (7.2°F)
11
6.0°C (10.8°F)
15
Summary of Contents for RX09RMVJU9
Page 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications ...
Page 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1 ...
Page 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E ...