SiUS041829E
Service Diagnosis
Part 6 Service Diagnosis
69
Long beep: Both the left-side and right-side numbers correspond with the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to page 70.
6. Press
Mode
button.
The right-side number blinks.
7. Press
Temp
or
Temp
button and change the number until you hear the long beep.
8. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the right-
side number does not.
Long beep: Both the left-side and right-side numbers correspond with the error code.
9. Determine the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to page 70.
10.Press
Mode
button for 5 seconds to exit from the service check mode.
When the remote controller is left untouched for 60 seconds, it returns to the normal mode also.
(R24047)
(R11673)
(R24048)
(R24047)
Summary of Contents for RX09RMVJU9
Page 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications ...
Page 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1 ...
Page 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E ...