SiUS041829E
Troubleshooting
Part 6 Service Diagnosis
83
4.9 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
Error Code
UA
Method of Error
Detection
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor/outdoor transmission signal.
Error Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
(R20435)
Caution
N
O
YES
YES
N
O
Match the compati
b
le models.
OK?
Correct the connection.
Check the code num
b
ers
(2P012345, for example) of the
indoor and outdoor unit PCB
w
ith the Parts List.
If not matched, change for the
correct PCB.
Are the
connecting
w
ires connected
properly?
Check the
com
b
ination of the
indoor
and outdoor unit.
Be sure to turn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.