4.16 Discharge Pipe Temperature Control
Error Code
F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above
A
, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below
B
.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
If the frequency drops, the temperature is lowered in compensation.
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01
Check No.12
Check No.14
When replacing the defective thermistor(s), replace the thermistor as ASSY.
A
B
°C
°F
°C
°F
09/12 class
110
230
88
190.4
18 class
110
230
95
203
(R20417)
Caution
NG
OK
OK
OK
NG
NG
∗
Discharge pipe thermistor
∗
O
u
tdoor heat exchanger thermistor
∗
O
u
tdoor temperat
u
re thermistor
∗
Refrigerant shortage
∗
Fo
u
r way valve
∗
Water mixed
∗
Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check proced
u
re.
Replace the o
u
tdoor
u
nit
PCB (main PCB).
Be s
u
re to t
u
rn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Summary of Contents for RX09RMVJU9
Page 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications ...
Page 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1 ...
Page 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E ...