Part 6 Service Diagnosis
119
5.10 Discharge Pressure Check
Check No.18
5.11 Outdoor Fan System Check
Check No.19
DC motor
(R21121)
YES
YES
YES
NO
NO
NO
NO
YES
Is the air filter or
indoor/o
u
tdoor heat
exchanger dirty?
Is the
connection pipe deformed?
Is the stop valve
open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor/o
u
tdoor heat exchanger.
Replace the compressor.
Discharge press
u
re check
(R21195)
YES
NO
NO
YES
O
u
tdoor fan system is f
u
nctioning.
Check the o
u
tdoor fan system.
Reconnect the connector.
Is
the o
u
tdoor fan
r
u
nning?
Fan motor lead
wire connector
disconnected?
Go to
Check No. 16
.