Field Settings
Part 7 Trial Operation and Field Settings
129
Caution
4. Field Settings
4.1 Temperature Display Switch
Procedure
Press the upper side of
Temp
button and
On
button at the same time for 5 seconds to change
the unit of temperature display.
4.2 When 2 Units are Installed in 1 Room
Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding wireless
remote controller can be set for different address.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB
1. Remove the front grille.
2. Remove the shield plate of the electrical box.
3. Cut the address setting jumper JA on the PCB.
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
(R22009)
JA
(Bottom of electrical box)
ADDRESS : JA
EXIST : 1
CUT : 2
(R21128)