Part 3 Printed Circuit Board Connector Wiring Diagram
21
Caution
2.2 RX18RMVJU9
Main PCB
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
1)
S20
Connector for electronic expansion valve coil
2)
S40
Connector for overload protector
3)
S70
Connector for DC fan motor
4)
S80
Connector for four way valve coil
5)
S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
6)
HL1, HN1, S
Connector for terminal block
7)
E1, E2
Terminal for ground
8)
U, V, W
Connector for compressor
9)
FU1, FU2
Fuse (3.15 A, 250 V)
10)
FU3
Fuse (30 A, 250 V)
11)
J6
Jumper for facility setting
Refer to page 131 for details.
12)
LED A
LED for service monitor (green)
13)
V1, V2, V3
Varistor
LED A
U, V, W
2P443814-55
FU2
V1
FU1
V3
V2
E1, E2
HL1, HN1, S
FU3
S80
S20
S40
S90
J6