Wiring

 WARNING

1) Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

3) Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)

 

(This unit uses an inverter, which means that it must be used an earth leakage breaker capable handling harmonics in order to 
prevent malfunctioning of the earth leakage breaker itself.)

4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
5) Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn ON the power supply until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wirings between the 

indoor and outdoor units 

so that the terminal 

numbers match.

 Tighten the terminal screws 

securely. We recommend a flathead 
screwdriver be used to tighten the screws. 
The screws are packed with the terminal 
board.

Observe the notes mentioned below when wiring to the power supply terminal board.

 

Precautions to be taken for power supply wiring. 

 

Use a round crimp-style terminal for connection to the power supply  terminal board. 
In case it cannot be used due to unavoidable reasons, be sure to observe the follow-
ing instruction.
Place the round crimp-style terminals on the wires up to the covered part and 
secure in place.

 CAUTION

When connecting the inter-unit wirings to the terminal board using a single core wire, be sure to perform curling.

 

Problems with the work may cause heat and fires.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

1
2
3

1 2 3

L

N

F

u

se 

20A

Earth leakage 
circ

u

it 

b

reaker

Earth

W

hen 

w

ire length exceeds 10m, 

u

se 2.0mm diameter 

w

ires.

H05R

N

Firmly fix the 

w

ires 

w

ith 

the terminal scre

w

s.

O

u

tdoor 

u

nit

Indoor 

u

nit

Po

w

er s

u

pply

50Hz 220-240

V

Firmly fix the 

w

ires 

w

ith 

the terminal scre

w

s.

Use 2.0mm diameter 

w

ires.

1

2

3

1

2

3

Power supply
terminal block

Shape wires so 
that the stop valve 
cover fit securely.

Firmly secure wire retainer so wire 
terminations will not receive external stress.

Use the specified wire type 
and connect it securely.

Stranded Wire

Round crimp-style
terminal

Strip wire end
to this point.

Excessive strip length
may cause electrical
shock or leakage.

Good

Wrong

Stripping wire at terminal block

3P377531-1A.book  Page 9  Monday, September 8, 2014  1:01 PM

Summary of Contents for RXL25M2V1B

Page 1: ...OR UNIT INSTALLATION MANUAL MODEL RXL25M2V1B RXLS25M2V1B RXL35M2V1B RXLS35M2V1B RXL25M3V1B ARXL25M2V1B RXL35M3V1B ARXL35M2V1B RXLG25M2V1B RXLG35M2V1B 3P377531 1A book Page 1 Monday September 8 2014 1...

Page 2: ...3P377531 1A book Page 2 Monday September 8 2014 1 01 PM...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 4: ...nhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b...

Page 5: ...or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the...

Page 6: ...ything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient tempera ture be sure to follow...

Page 7: ...g use foot bolts or wires 250mm from wall unit mm How to remove the stop valve cover Remove the screw on the stop valve cover Slide the cover downward to remove it How to attach the stop valve cover I...

Page 8: ...of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their length are 20mm...

Page 9: ...htening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wren...

Page 10: ...d to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuu...

Page 11: ...sulation dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D...

Page 12: ...s the indoor unit operation stop button Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button and the operation select button at...

Page 13: ...w when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be...

Page 14: ...apacitor DB1 DB2 DB3 Diode bridge FU1 FU2 FU3 Fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MRCW MRM10 MRM20 MR30 Magnetic relay N Neutral PCB1 Print...

Page 15: ...of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to s...

Page 16: ...3P377531 1A book Page 1 Monday September 8 2014 1 01 PM...

Page 17: ...3P377531 1A book Page 1 Monday September 8 2014 1 01 PM...

Page 18: ...3P377531 1A 2014 07 Copyright 2014 Daikin 3P377531 1A book Page 1 Monday September 8 2014 1 01 PM...

Reviews: