background image

RX(Y)Q5-10-1 RXQ RXYQ
RXYHQ1 RX(Y)Q14~18P7W1BA
VRVIII System air conditioner
4PW48461-1

Installation manual

20

11.5. Additional refrigerant charge

There are two ways to charge refrigerant. Use the selected method
following the described procedure below.

Adding refrigerant using leak detection function.
Refer to 

"1 Adding refrigerant using leak detection function" on

page 20

Adding refrigerant without using leak detection function.
Refer to 

"2 Adding refrigerant without using leak detection

function" on page 22

Follow the procedures below.

1

Adding refrigerant using leak detection function

The automatic refrigerant charging has limits as described
below.
At out of limit, the system can not operate the automatic
refrigerant charging.

To speed up the proces of charging refrigerant for large systems, it is
recommended to first manually charge a portion of the refrigerant
first before performing automatic charging.

1

Calculate how much refrigerant to be added using the formula
explained in the chapter 

"How to calculate the additional

refrigerant to be charged" on page 10

.

2

The amount of pre-charging is 10 kg less than the calculated
amount.

3

Open valve C (valves A and B and the stop valves must be left
closed) and charge the refrigerant in liquid form via the liquid
side stop valve service port.

(See figure 28)

3

Monitor mode

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Selection status of how many 
connected indoor units to 
display.

c x

x

x w x w

OR

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Selection status of how many 
connected outdoor units to 
display. 

c x

x w x

x

x

Pressing the 

 

button causes the LED display to show the 

data on the number of indoor units that are connected or how many 
outdoor units that are connected in a multiple outdoor unit system.

4

Monitor mode

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Displaying the number of 
connected indoor units

c x c x c c x

32

16

8

4

2

1

Calculate the number of connected indoor units by adding the values of 
all (H2P~H7P) blinking (

c

) LEDs together. 

In this example: 16+4+2=22 units

Press the 

 

button to return to step 1, setting mode 1 

(H1P= 

x

 "OFF").

Adding refrigerant using the automatic refrigerant charging
function is recommended.

If refrigerant is added manually, without using the
automatic refrigerant charging function, the refrigerant leak
detection function can not be used.

When charging a system, charging over the
permissible quantity can cause liquid hammer.

Always use protective gloves and protect your eyes
when charging refrigerant.

When the refrigerant charging procedure is done or
when pausing, close the valve of the refrigerant tank
immediately. If the tank is left with the valve open, the
amount of refrigerant which is properly charged may
get off point. More refrigerant may be charged by any
remaining pressure after the unit has stopped.

Electric shock warning

Close the electric box lid before turning on the main
power.

Perform the settings on the circuit board (A1P) of the
outdoor unit and check the LED display after the
power is on via the service lid which is in the lid of the
electric box. 
Operate switches with an insulated
stick (such as a ball-point pen) to
avoid touching the life parts. 
Make sure to re-attach the
inspection cover into the switch box cover after the job
is finished.

BS3  RETURN

BS1  MODE

If the power of some units is turned off, the charging
procedure can not be finished properly.

In case of a multiple outdoor system, turn on the
power of all outdoor units.

Make sure to turn ON the power 6 hours before
starting the operation. This is necessary to warm the
crankcase by the electric heater.

If operation is performed within 12 minutes after the
indoor and outdoor units are turned on, the H2P-LED
will be lit and the compressor will not operate.

NOTE

See

 

"11.3. Stop valve operation procedure" on

page 19

 for details on how to handle stop valves.

The refrigerant charging port is connected to the
piping inside the unit.
The unit’s internal piping is already factory
charged with refrigerant, so be careful when
connecting the charge hose.

After adding the refrigerant, do not forget to close
the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to
13.9 N•m. 

In order to ensure uniform refrigerant distribution,
it may take the compressor ±10 minutes to start
up after the unit has started operation. This is not
a malfunction.

Outdoor temperature

: 0°C DB~43°C DB

Indoor temperature

: 20°C DB~32°C DB

Total indoor unit capacity

80%

1

Measuring instrument

2

Tank (siphon system)

3

Charge hose

4

Liquid line stop valve

5

Gas line stop valve

6

Stop valve service port

7

Valve B

8

Valve C

9

Valve A

10

Outdoor unit

11

Refrigerant charge port

12

To indoor unit

13

Interunit piping

14

Refrigerant flow

Summary of Contents for RXYHQ12P8W1B

Page 1: ...ION MANUAL RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA RXYQ5P7W1B RXYQ8P8W1B RXYQ10P7W1B RXYQ12P7W1B RXYHQ12P8W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA System air co...

Page 2: ...Q16 36 RX Y Q5 RX Y Q8 18 RXYHQ12 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 5...

Page 3: ...UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O...

Page 4: ...a 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych norm i innych dokument w normalizacyjnych pod warun...

Page 5: ...yll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...ndoor units for air conditioning purposes and suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the RX Y Q P RXYHQ units Installation...

Page 7: ...Q54 RXYQ18 RXYQ18 RXYQ18 675 1755 64 Standard combination of outdoor units Total capacity of indoor units Total quantity of indoor units RXYHQ12 a a main unit 150 390 30 RXYHQ16 RXYQ8 RXYQ8 200 520 32...

Page 8: ...ave obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due to leakage of inflammable gas 4 Ensure that water can not cau...

Page 9: ...fore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m...

Page 10: ...is to be installed on a frame install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corros...

Page 11: ...as shown in the figure 2 Removing the pinched piping When connecting refrigerant piping to the outdoor unit first remove the pinched piping Do not vent gases into the atmosphere Removing of the pinche...

Page 12: ...into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping betwe...

Page 13: ...stallation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level d...

Page 14: ...kits can only be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the c...

Page 15: ...YQ34P 1x 16 1x 18 If the outdoor unit is RXYQ34P and the piping lengths are as below B A C D E B B Outdoor unit capacity type Piping size outer diameter mm Gas pipe Liquid pipe RX Y Q5 15 9 9 5 RX Y Q...

Page 16: ...ength of above pipes must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p...

Page 17: ...lator R10 Resistor current sensor A4P A8P R31T 33T Thermistor discharge M1C M3C R50 59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure swi...

Page 18: ...mm2 RXYQ30 3 N 50 Hz 400 V 55 2 A 63 A 0 75 1 25 mm2 RXYQ32 3 N 50 Hz 400 V 63 0 A 80 A 0 75 1 25 mm2 RXYQ34 3 N 50 Hz 400 V 64 0 A 80 A 0 75 1 25 mm2 RXYQ36 3 N 50 Hz 400 V 65 0 A 80 A 0 75 1 25 mm2...

Page 19: ...bnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of...

Page 20: ...h protective tape in order to prevent damage to the wires put the wires through field supplied protective wire conduits at that location or install suitable field supplied wire nipples or rubber bushi...

Page 21: ...ow the limits below If the unit to unit cables are beyond these limits it may result in malfunction of transmission Maximum wiring length 1000 m Total wiring length 2000 m Maximum interunit wiring len...

Page 22: ...are established When disconnecting the power supply cord the current carrying connections must be separated before the earth connection is Length of the conductors between the power supply cord anchor...

Page 23: ...additional charging For charging the additional refrigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinat...

Page 24: ...uid refrigerant with the cylinder in upright position Charge the liquid refrigerant with the cylinder in up side down position Charging with an unsuitable substance may cause explosions and accidents...

Page 25: ...ing function the refrigerant leak detection function can not be used When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your...

Page 26: ...d press the button once As long as the button is not pressed the system will remain in heating mode This can be required to increase the indoor temperature 10 Press the button to perform the temperatu...

Page 27: ...nd B and the stop valves must be left closed and charge the required amount of refrigerant through the liquid side stop valve service port When the required amount of refrigerant is fully charged clos...

Page 28: ...hown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure When the charging amount is little the PE code may not be displayed...

Page 29: ...ing refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded LED display Default status before delivery Micro computer operation monitor M...

Page 30: ...sulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution w...

Page 31: ...n wiring and cool heat selection on page 16 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING...

Page 32: ...n level setting via the external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consu...

Page 33: ...f the operation is completed Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again...

Page 34: ...gerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of...

Page 35: ...n level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done...

Page 36: ...NOTES NOTES...

Page 37: ...3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 30 13 14 3 5 4 2 1 7 8 9 6 10 10...

Page 38: ...4PW48461 1 Copyright Daikin...

Reviews: