RX(Y)Q5-10-1 RXQ RXYQ
RXYHQ1 RX(Y)Q14~18P7W1BA
VRVIII System air conditioner
4PW48461-1
Installation manual
28
In case refrigerant was added by using the leak detection
function
■
In the check operation, the following checks and judgements will
be performed:
■
Check of the stop valve opening
■
Check for wrong wiring
■
Judgement of piping length
■
Judgement of initial refrigerant state
■
It takes ±3 hours (if the outdoor temperature is low, it takes
±4 hours) to complete the check operation.
■
The system can not perform the judgement of initial refrigerant
state in the following cases:
■
The outdoor temperature is out of range
(<0°C DB or >43°C DB)
■
The indoor temperature is out of range
(<20°C DB or >32°C DB)
■
A forced OFF during the test operation
In this case, after performing the check operation, normal
operation is possible although the abnormality code
U3
is
displayed on the indoor remote controller and the refrigerant
leakage detection function can not be used.
Perform the check operation again and complete the judgement
of initial refrigerant state.
Perform the test operation as decribed in the paragraph
"Test
operation procedure" on page 28
.
In case refrigerant was added without using the leak
detection function (charging in cooling mode)
■
In the check operation, the following checks and judgement will
be performed:
■
Check of the stop valve opening
■
Check for wrong wiring
■
Judgement of piping length
■
It takes ±30 minutes to complete the check operation.
Check operation procedure
1
Close the electric box lid and all front panels except the one on
the side of the electric box.
2
Turn on the power to the outdoor unit and all connected indoor
units. Be sure to turn the power ON at least 6 hours before
operation in order to have power running to the crank case
heater.
3
Make the field setting as needed using the push buttons on the
PCB (A1P) of the outdoor unit. Refer to
"12.3. Field setting" on
page 25
.
4
Set the check operation (without initial refrigerant decision)
following setting mode 2 in the field setting and perform the
check operation.
The system operates for ±30 minutes and automatically stops
the check operation.
■
If no malfunction code is displayed on the remote controller
after the system has stopped, check if the operation is
completed. Normal operation will be possible after 5 minutes.
■
If a malfunction code is displayed on the remote controller,
correct the malfunction and perform the check operation
again as decribed in
"Correcting after abnormal completion
of the test operation" on page 29
In case refrigerant was added without using the leak
detection function (pre-charging, charging in heating mode)
■
In the check operation, the following checks and judgement will
be performed:
■
Check of the stop valve opening
■
Check for wrong wiring
■
Check of refrigerant overcharge
■
Judgement of piping length
■
It takes ±40 minutes to complete the check operation.
Perform the test operation as decribed in the paragraph
"Test
operation procedure" on page 28
.
Test operation procedure
1
Close all front panels except the front panel of the electric box.
2
Turn ON the power to all outdoor units and the connected indoor
units.
Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.
3
Make the field setting as described in the paragraph
"12.3. Field
setting" on page 25
.
4
Press the
button once, and set to the SETTING
MODE (H1P LED = OFF).
5
Press and hold the
button down for 5 seconds or
more. The unit will start the test operation.
■
The test operation is automatically carried out in cooling
mode, the H2P LED will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.
■
It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.
■
During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the LED display may change, but these are not mal-
functions.
■
During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the
button. The unit will stop after
±30 seconds.
6
Close the front panel in order to let it not be the cause of
misjudgement.
7
Check the test operation results by the LED display on the
outdoor unit.
8
When the test operation is fully completed, normal operation will
be possible after 5 minutes.
Otherwise, refer to
"Correcting after abnormal completion of the
test operation" on page 29
to take actions for correcting the
abnormality.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Normal completion
x
x w x
x
x
x
Abnormal completion
x w w x
x
x
x
BS1 MODE
BS4 TEST
BS3 RETURN
Summary of Contents for RXYHQ12P8W1B
Page 36: ...NOTES NOTES...
Page 38: ...4PW48461 1 Copyright Daikin...