5 Installation
Installation and operation manual
15
RXYSQ4~Y1B
VRV IV-S system air conditioner
4P397284-1 – 2015.05
e
d
F1/F2
(16 V)
F1/F2
(16 V)
220-240 V
1~ 50 Hz
c
a
Y1
V1
b
220-240 V
1~ 50 Hz
380-415 V
3N~ 50 Hz
a
Main switch
b
Earth connection
c
Power supply wiring (including earth) (sheathed cable)
F1/F2
Transmission wiring (sheathed cable)
V1
Outdoor unit (RXYSQ4~6_V1)
Y1
Outdoor unit (RXYSQ4~6_Y1)
d
Indoor unit
e
User interface
5.7.2
Guidelines when knocking out knockout
holes
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After making the knockout holes, we recommend you
remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage.
b
c
a
a
Knockout hole
b
Burr
c
Sealant etc.
5.7.3
Guidelines when connecting the electrical
wiring
Tightening torques
Wiring
Screw size
Tightening torque
(N•m)
Power supply wiring
(power
shielded ground)
M5
2.2~2.7
Transmission wiring
M3.5
0.8~0.97
5.7.4
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover.
2
Connect the transmission wiring as follows:
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
a
b
X2M
TO OUT/D
TO IN/D
a
Use the conductor of sheathed wire (2 wire) (no polarity)
b
Terminal board (field supply)
WARNING
You must use shielded wire and connect the earth to the
transmission terminal (X2M).
C/H SELECTOR
A B C
F1 F2 F1 F2
TO IN/D
UNIT
V1
Y1
F1 F2 F1 F2
TO IND TO OUTD
TO OUT/D
UNIT
a
a
a
Earth
3
Connect the power supply as follows:
1~ 50 Hz
220-240 V
L
L
N
V1
Y1
X1M
3N~ 50 Hz
380-415 V
L1 L2 L3
L1 L2 L3
N
X1M
a
b
c
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable
4
Fix the cables (power supply and transmission wiring) with
cable ties.
Summary of Contents for RXYSQ5T7V1B
Page 34: ......
Page 35: ......
Page 36: ...4P397284 1 0000000V 4P397284 1 2015 05 Copyright 2015 Daikin...