5 Installation
Installation and operation manual
13
RXYSQ6T7Y1B9
VRV IV-S system air conditioner
4P397285-1B – 2016.03
If
Then
Too much
refrigerant is
charged
Recover refrigerant.
Disconnect the manifold from
the liquid line.
You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.
The determined additional
refrigerant amount is
not
reached
yet
Disconnect the manifold from
the liquid line.
Continue with the "Charging
refrigerant (in manual
additional refrigerant charge
mode)" instructions.
Charging refrigerant (in manual additional refrigerant charge
mode)
The remaining additional refrigerant charge can be charged by
operating the outdoor unit by means of the manual additional
refrigerant charge mode.
5
Connect as shown. Make sure valve A is closed.
p< p>
R410A
a
c
d
b
A
d
a
Weighing scales
b
Refrigerant R410A tank (siphon system)
c
Vacuum pump
d
Refrigerant charge port
A
Valve A
NOTICE
The refrigerant charging port is connected to the piping
inside the unit. The unit's internal piping is already factory
charged with refrigerant, so be careful when connecting
the charge hose.
6
Open all outdoor unit stop valves. At this point, valve A must
remain closed!
7
Take all the precautions mentioned in
into account.
8
Turn on the power of the indoor units and outdoor unit.
9
Activate setting [2‑20] to start the manual additional refrigerant
charge mode. For details, see
"6.1.8 Mode 2: Field settings" on
.
Result:
The unit will start operation.
INFORMATION
The manual refrigerant charge operation will automatically
stop within 30 minutes. If charging is not completed after
30 minutes, perform the additional refrigerant charging
operation again.
INFORMATION
▪ When a malfunction is detected during the procedure
(e.g., in case of closed stop valve), a malfunction code
will be displayed. In that case, refer to
codes when charging refrigerant" on page 13
and
solve the malfunction accordingly. Resetting the
malfunction can be done by pushing BS3. You can
restart the "Charging" instructions.
▪ Aborting the manual refrigerant charge is possible by
pushing BS3. The unit will stop and return to idle
condition.
10
Open valve A.
11
Charge refrigerant until the remaining determined additional
refrigerant amount is added, and then close valve A.
12
Press BS3 to stop the manual additional refrigerant charge
mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
NOTICE
After adding the refrigerant, do not forget to close the lid of
the refrigerant charging port. The tightening torque for the
lid is 11.5 to 13.9 N•m.
5.6.4
Error codes when charging refrigerant
INFORMATION
If a malfunction occurs, the error code is displayed on the
user interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the
malfunction code and take corresponding action,
problems based on error codes" on page 22
5.6.5
To fix the fluorinated greenhouse gases
label
1
Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of
a
.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Greenhouse gas emissions
of the total refrigerant charge
expressed as tonnes CO
2
-equivalent
f
GWP = Global warming potential
NOTICE
In Europe, the
greenhouse gas emissions
of the total
refrigerant charge in the system (expressed as tonnes
CO
2
-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000