8 Troubleshooting

Installation and operation manual

22

RXYSQ6T7Y1B9

VRV IV-S system air conditioner

4P397285-1B – 2016.03

Step

Description

Pump down operation

Unit stop

INFORMATION

During the test operation, it is not possible to stop the unit
operation  from  a  user  interface.  To  abort  the  operation,
press BS3. The unit will stop after ±30 seconds.

4

Check  the  test  operation  results  on  the  outdoor  unit  7‑LEDs
display.

Completion

Description

Normal
completion

Abnormal
completion

Refer to 

"7.3.3 Correcting after abnormal

completion of the test run" on page 22

 to take

actions for correcting the abnormality. When
the test operation is fully completed, normal
operation will be possible after 5 minutes.

7.3.3

Correcting after abnormal completion of
the test run

The test operation is only completed if there is no malfunction code
displayed.  In  case  of  a  displayed  malfunction  code,  perform
correcting actions as explained in the malfunction code table. Carry
out  the  test  operation  again  and  confirm  that  the  abnormality  is
properly corrected.

INFORMATION

If a malfunction occurs, the error code is displayed on the
user interface of the indoor unit.

INFORMATION

Refer to the installation manual of the indoor unit for other
detailed malfunction codes related to indoor units.

7.3.4

Operating the unit

Once  the  unit  is  installed  and  test  operation  of  outdoor  unit  and
indoor units is finished, the operation of the system can start.

For  operating  the  indoor  unit,  the  user  interface  of  the  indoor  unit
should be switched ON. Refer to the indoor unit operation manual for
more details.

8

Troubleshooting

8.1

Solving problems based on error
codes

In  case  of  a  displayed  malfunction  code,  perform  correcting  actions
as explained in the malfunction code table.

After correcting the abnormality, press BS3 to reset the malfunction
code and retry operation.

INFORMATION

If a malfunction occurs, the error code is displayed on the
user interface of the indoor unit.

8.1.1

Error codes: Overview

Main code

Cause

Solution

▪ The stop valve of an outdoor unit is left closed.

▪ Refrigerant overcharge

▪ Open the stop valve on both the gas and liquid side.

▪ Recalculate  the  required  amount  of  refrigerant  from  the

piping  length  and  correct  the  refrigerant  charge  level  by
recovering  any  excessive  refrigerant  with  a  refrigerant
recovery machine.

▪ The stop valve of an outdoor unit is left closed.

▪ Insufficient refrigerant

▪ Open the stop valve on both the gas and liquid side.

▪ Check  if  the  additional  refrigerant  charge  has  been

finished  correctly.  Recalculate  the  required  amount  of
refrigerant  from  the  piping  length  and  add  an  adequate
amount of refrigerant.

Electronic expansion valve malfunction

(Y1E) - A1P (X21A)

(Y3E) - A1P (X22A)

Check connection on PCB or actuator.

▪ The stop valve of an outdoor unit is left closed.

▪ Insufficient refrigerant

▪ Open the stop valve on both the gas and liquid side.

▪ Check  if  the  additional  refrigerant  charge  has  been

finished  correctly.  Recalculate  the  required  amount  of
refrigerant  from  the  piping  length  and  add  an  adequate
amount of refrigerant.

Refrigerant overcharge

Recalculate the required amount of refrigerant from the
piping length and correct the refrigerant charge level by
recovering any excessive refrigerant with a refrigerant
recovery machine.

Ambient temperature sensor malfunction (R1T) - A1P
(X11A)

Check connection on PCB or actuator.

Discharge temperature sensor malfunction (R2T): open
circuit / short circuit - A1P (X12A)

Check connection on PCB or actuator.

Suction temperature sensor malfunction

(R3T) - A1P (X12A)

(R5T) - A1P (X12A)

Check connection on PCB or actuator.

Summary of Contents for RXYSQ6T7Y1B9

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6T7Y1B9...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...em da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytu...

Page 4: ...king field settings 16 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 17 6 1 6 To use mode 2 17 6 1 7 Mode 1 and d...

Page 5: ...aper in the box of the outdoor unit Outdoor unit installation and operation manual Installation and operation instructions Format Paper in the box of the outdoor unit Installer and user reference guid...

Page 6: ...cid deoxidised seamless copper for refrigerant Foreign materials inside pipes including oils for fabrication must be 30 mg 10 m 4 2 2 Refrigerant piping material Piping material Phosphoric acid deoxid...

Page 7: ...r unit capacity type HP Refrigerant branch kit 6 KHRQ22M20T Refnet joints at other branches For refnet joints other than the first branch select the proper branch kit model based on the total capacity...

Page 8: ...the foundation to drain waste water surrounding the unit Avoid drain water flowing over the footpath so that it does not become slippery in case of ambient freezing temperatures If you install the un...

Page 9: ...rader type valve After handling the service port make sure to tighten the service port cover securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening th...

Page 10: ...This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explained 2 methods for initial installation leak...

Page 11: ...mum operation pressure of the unit i e 4 0 MPa 40 bar 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommended b...

Page 12: ...s original amount of refrigerant refer to the nameplate on the unit and the determined additional refrigerant amount 5 6 2 To determine the additional refrigerant amount INFORMATION For final charge a...

Page 13: ...e will be displayed In that case refer to 5 6 4 Error codes when charging refrigerant on page 13 and solve the malfunction accordingly Resetting the malfunction can be done by pushing BS3 You can rest...

Page 14: ...ut holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when connecting the electrical wiring Tightening torques Wiring Screw size T...

Page 15: ...he edge of the knockout hole from cutting the wires a b c d e A B A Inside of the outdoor unit B Outside of the outdoor unit a Wire b Bush c Nut d Frame e Hose 6 Reattach the service cover 7 Connect a...

Page 16: ...setting components The components to make field settings are as follows BS2 SET BS1 MODE BS3 RETURN BS4 TEST BS5 RESET H1P H2P H3P H4P H5P H6P H7P H8P A1P A2P X1M X2M 1 2 OFF ON DS1 MULTI DEMAND L N O...

Page 17: ...P ON Unit is currently operating under low noise restrictions Example 7 LEDs display Mode 1 You can read out setting 1 5 the total number of connected indoor units as follows Action Button display 1 S...

Page 18: ...e at the selected power consumption limitation The second method is to enable power consumption limitation based on an external input For this operation an optional accessory is required 7 LEDs displa...

Page 19: ...ing the field setting again 2 21 Refrigerant recovery vacuuming mode In order to achieve a free pathway to reclaim refrigerant out of the system or to remove residual substances or to vacuum the syste...

Page 20: ...s setting is used in conjunction with setting 2 8 Eco default Mild Quick Powerful 2 42 Heating comfort setting This setting is used in conjunction with setting 2 9 Eco default Mild Quick Powerful 6 1...

Page 21: ...or any other material Additional refrigerant charge The amount of refrigerant to be added to the unit shall be written on the included Added refrigerant plate and attached to the rear side of the fron...

Page 22: ...erform correcting actions as explained in the malfunction code table After correcting the abnormality press BS3 to reset the malfunction code and retry operation INFORMATION If a malfunction occurs th...

Page 23: ...the specified indoor unit are not connected correctly to the outdoor unit Open the stop valve on both the gas and liquid side Confirm that the piping and wiring of the specified indoor unit are connec...

Page 24: ...refer to the installation manual of the option 3 Refer to the installation or service manual on how to use BS1 BS4 push buttons and DS1 1 and DS1 2 DIP switches 4 Do not operate the unit by short cir...

Page 25: ...Detailed information on required actions to achieve certain functions can be found in the dedicated installation and operation manual of the indoor unit Refer to the operation manual of the installed...

Page 26: ...ating or cooling operation b COOL HEAT CHANGEOVER SWITCH Set the switch to for cooling or to for heating To start 1 Select operation mode with the cool heat changeover switch as follows Cooling operat...

Page 27: ...The air flow flap itself adjusts its position The air flow direction can be fixed by the user Automatic and desired position WARNING Never touch the air outlet or the horizontal blades while the swin...

Page 28: ...ontact your dealer and keep the warranty card at hand 13 2 2 Recommended maintenance and inspection Since dust collects when using the unit for several years performance of the unit will deteriorate t...

Page 29: ...malfunction code reset the code by pushing the ON OFF button If not ask your installer for advice Main code Contents External protection device was activated EEPROM failure indoor Drain system malfun...

Page 30: ...display The fan direction does not swing This is because the unit is being controlled by the micro computer 14 2 6 Symptom White mist comes out of a unit Indoor unit When humidity is high during cooli...

Page 31: ...operation This is to prevent refrigerant from remaining in the compressor The unit will stop after 5 to 10 minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped...

Page 32: ...4P397285 1 B 00000005 4P397285 1B 2016 03 Copyright 2015 Daikin...

Reviews: