10 About the system
Installation and operation manual
25
RXYSQ6T7Y1B9
VRV IV-S system air conditioner
4P397285-1B – 2016.03
S2S
Cool/heat selector switch (option)
V1R
IGBT power module (A2P)
V2R, V3R
Diode module (A2P)
X*A
PCB connector
X*M
Terminal strip
X*Y
Connector
X37A
Connector (power supply for option PCB)
Y1E
Electronic expansion valve (main)
Y3E
Electronic expansion valve (subcool heat exchanger)
Y1S
Solenoid valve (4‑way valve)
Z*C
Noise filter (ferrite core)
Z*F
Noise filter
For the user
10
About the system
The indoor unit part of VRV IV-S heat pump system can be used for
heating/cooling applications. The type of indoor unit which can be
used depends on the outdoor units series.
NOTICE
Do not use the air conditioner for other purposes. In order
to avoid any quality deterioration, do not use the unit for
cooling precision instruments, food, plants, animals or
works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future
system extensions) is available in technical engineering
data and should be consulted. Contact your installer to
receive more information and professional advice.
10.1
System layout
d
d
c
c
b
a
a
VRV IV-S Heat pump outdoor unit
b
Refrigerant piping
c
VRV direct expansion (DX) indoor unit
d
User interface (dedicated depending on indoor unit type)
11
User interface
CAUTION
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen.
For checking and adjusting the internal parts, contact your
dealer.
This operation manual will give a non-exhaustive overview of the
main functions of the system.
Detailed information on required actions to achieve certain functions
can be found in the dedicated installation and operation manual of
the indoor unit.
Refer to the operation manual of the installed user interface.
12
Operation
12.1
Operation range
Use the system in the following temperature and humidity ranges for
safe and effective operation.
Cooling
Heating
Outdoor
temperature
–5~46°C DB
–20~21°C DB
–20~15.5°C WB
Indoor
temperature
21~32°C DB
14~25°C WB
15~27°C DB
Indoor humidity
≤80%
(a)
(a)
To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.
Above operation range is only valid in case direct expansion indoor
units are connected to the VRV IV-S system.
12.2
Operating the system
12.2.1
About operating the system
▪ Operation procedure varies according to the combination of
outdoor unit and user interface.
▪ To protect the unit, turn on the main power switch 6 hours before
operation.
▪ If the main power supply is turned off during operation, operation
will restart automatically after the power turns back on again.
12.2.2
About cooling, heating, fan only, and
automatic operation
▪ Changeover cannot be made with a user interface whose display
shows
"change-over under centralised control" (refer to
installation and operation manual of the user interface).
▪ When the display
"change-over under centralised control"
flashes, refer to
"12.5.1 About setting the master user
▪ The fan may keep on running for about 1 minute after the heating
operation stops.
▪ The air flow rate may adjust itself depending on the room
temperature or the fan may stop immediately. This is not a
malfunction.
12.2.3
About the heating operation
It may take longer to reach the set temperature for general heating
operation than for cooling operation.