SiK401004_A
33
FUNCTION CONTROL
2.2 Dry Mode
Dry mode operation is as follows
T
amb
≥
T
set
+2
C: Cooling mode will be entered. In that case, the compressor and outdoor
unit fan runs and indoor unit fan runs at low speed.
T
amb
≤
T
set
-2
C: Cooling OFF status will be entered. In that case, the compressor and
outdoor unit fan stop running.
T
set
-2
C<T
amb
<T
set
+2
C: ON-OFF alternated status will be entered. In that case, after
compressor is running for continuous 6min, it will stop for another continuous 4min, which
will be circularly executed. The indoor unit fan runs at low speed.
Dry Mode
Manual OFF