MAINTENANCE
E6
Malfunction of
communications
Communication
Check the communication state between the
indoor unit PCB and outdoor unit PCB by
micro-computer. Abnormality is detected
when the correct communication is not
conducted in 30se. When the malfunction of
communication occurs, the system will be
shut down the screen will display the
malfunction code (E6).The reset for the
communication failure is automatic reset.
E9
Malfunction of drain
water level
Liquid water level
Malfunction of darin water level is detected
when the liquid water level switch opens for
more than 8sec. the screen will display the
malfunction code (E9). The reset for fill water
protection is manual reset.
F0
Malfunction of indoor
room temperature
thermistor at air intake
Indoor room
thermistor
Malfunction of indoor room temperature
thermistor at air intake is detected when a short
circuit or an open circuit in the indoor room
temperature thermistor for more than 5 sec.
The indoor room temperature value will be set
as 24°C forcibly. The reset for the malfunction
of indoor room temperature thermistor is
automatic reset. If the malfunction of indoor
room temperature thermistor will be reset in air
supply mode, the malfunction code (F0) will
disappear on the screen and the indoor unit fan
will run normally.
F1
Malfunction of
evaporator temperature
thermistor
Evaporator
temperature
thermistor
Malfunction of evaporator temperature
thermistor is detected when a short circuit or an
open circuit in the evaporator temperature
thermistor for more than 5 sec. The system will
be shut down in cooling operation and
dehumidifying operation. The screen will
display the malfunction code (F1) on the
screen. The reset for the malfunction of
evaporator temperature thermistor is automatic
reset. In air supply mode, the screen will
display the malfunction code (F1) on the
screen. However, the indoor unit fan will run
normally in this case.
F2
Malfunction of
condenser temperature
thermistor
Condenser
temperature
thermistor
Malfunction of condenser temperature
thermistor is detected when a short circuit or an
open circuit in the condenser temperature
thermistor for more than 5 sec. The system will
be shut down in cooling operation and
dehumidifying operation. The screen will
display the malfunction code (F2) on the
screen. The reset for the malfunction of
condenser temperature thermistor is automatic
reset. In air supply mode, the screen will
display the malfunction code (F2) on the
screen. However, the indoor unit fan will run
normally in this case.
Summary of Contents for RY24PEV1K
Page 12: ...SiK401004_A SPECIFICATIONS 4 2 NOMENCLATURE 24 E K M V1...
Page 36: ...SiK401004_A SPECIFICATIONS 28 5 PIPING DIAGRAM...
Page 80: ...SiK401004_A INSTALLATION 72 2 5 Installation Clearance Data Figure 2 5 1...
Page 110: ...SiK401004_A MAINTENANCE 102 3 1 2 R24PEV1K 6 3 6 2 5 6 4 3...
Page 111: ...SiK401004_A 103 MAINTENANCE 3 1 3 RY30PEV1K 6 3 6 2 5 3 6 6...
Page 112: ...SiK401004_A MAINTENANCE 104 3 1 4 R30PEV1K 6 3 6 2 5 6 5 0...
Page 113: ...SiK401004_A 105 MAINTENANCE 3 1 5 RY36PEY1K...
Page 114: ...SiK401004_A MAINTENANCE 106 3 1 6 R36PEY1K L L...
Page 115: ...SiK401004_A 107 MAINTENANCE 3 1 7 RY42PEY1K RY48PEY1K L L...
Page 116: ...SiK401004_A MAINTENANCE 108 3 1 8 R42PEY1K R48PEY1K L L...