19
|
Configuration
Installer and user reference guide
133
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
[2‑25]
Description
1
Level 1
Level 3<Level 2<Level 1
2 (default)
Level 2
3
Level 3
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
[2‑26]
Start time automatic low noise operation
(approximately)
1
20h00
2 (default)
22h00
3
24h00
[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
[2‑27]
Stop time automatic low noise operation
(approximately)
1
6h00
2
7h00
3 (default)
8h00
[2‑30]
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 1. The level is according to the
table.
[2‑30]
Power consumption limitation (approximately)
1
60%
2
65%
3 (default)
70%
4
75%
5
80%
6
85%
7
90%
8
95%
[2‑31]
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62).