19
|
Configuration
Installer and user reference guide
135
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
[2‑81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"19.3 Energy saving and optimum operation"
[2‑82]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
[2‑82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"19.3 Energy saving and optimum operation"
[2‑83]
Master user interface allocation in case VRV DX indoor units and RA DX indoor
units are used at the same time.
By changing setting [2‑83], you can allow the VRV DX indoor unit to be the
operation mode selector (system power OFF/ON is required after applying this
setting).
[2‑83]
Description
0
VRV DX indoor unit has mode selection right.
1 (default)
RA DX indoor unit has mode selection right setting.
[2‑85]
Automatic leak detection interval time.
This setting is used in conjunction with setting [2‑86].
[2‑85]
Time between automatic leak detection executions
(days)
0 (default)
365
1
180
2
90
3
60
4
30
5
7
6
1
[2‑86]
Automatic leak detection activation.