background image

4 Installation

Installation manual

12

RZASG71~Y1

Sky Air Advance-series

4P485928-1 – 2017.04

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally does not leak. If the refrigerant leaks in the room
and comes in contact with fire from a burner, a heater, or a
cooker, this may result in fire, or the formation of a harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  from  which  you  purchased
the unit.

Do not use the unit until a service person confirms that the
portion from which the refrigerant leaked is repaired.

4.4.3

To determine the additional refrigerant
amount

To determine if adding additional refrigerant is necessary

If

Then

(L1+L2+L3+L4+L5+L6+L7)≤
30 m (chargeless length)

You do not have to add
additional refrigerant.

(L1+L2+L3+L4+L5+L6+L7)>
30 m (chargeless length)

You must add additional
refrigerant.

For future servicing, encircle the
selected amount in the tables
below.

INFORMATION

Piping length is the largest one way length of liquid piping.

To determine the additional refrigerant amount (R in kg) (in
case of pair)

L1 (m)

L1:

30~40 m

40~50 m

R:

0.35 kg

0.7 kg

To determine the additional refrigerant amount (R in kg) (in
case of twin, triple and double twin)

1

Determine R1 and R2.

If

Then

G1>30 m

Use the table below to determine
R1

G1≤30 m

(and G1+G2>30 m)

R1=0.0 kg.

Use the table below to determine
R2.

Length (total length of liquid piping−30 m)

0~10 m

10~20 m

20~30 m

30~40 m

40~45 m

R1:

0.35 kg

0.7 kg

1.05 kg

(a)

1.4 kg

(a)

R2:

0.2 kg

0.4 kg

0.6 kg

0.8 kg

(a)

1 kg

(b)

(a)

Only for RZASG100~140.

(b)

Only for R125.

2

Determine the additional refrigerant amount: R=R1+R2.

Examples

Layout

Additional refrigerant amount (R)

L2=7 m 

(Ø6.4 mm)
L3=5 m 

(Ø6.4 mm)

L1=35 m (Ø9.5 mm)

RZASG100

Case: Twin, standard liquid pipe size

1 G1 Total Ø9.5

 

=> G1=35 m

G2 Total Ø6.4 => G2=7+5=12 m

2 Case: G1>30 m

R1 Length=G1−30 m=5 m

=> R1=0.35 kg

R2 Length=G2=12 m

=> R2=0.4 kg

3 R

R=R1+R2=0.35+0.4=0.75 kg

L2=15 m 

(Ø6.4 mm)
L3=12 m 

(Ø6.4 mm)
L4=17 m 

(Ø6.4 mm)

L1=5 m (Ø9.5 mm)

RZASG125

Case: Triple, standard liquid pipe size

1 G1 Total Ø9.5 => G1=5 m

G2 Total Ø6.4 => G2=15+12+17=44 m

2 Case: G1≤30 m (and G1+G2>30 m)

R1 R1=0.0 kg

R2 Length=G1+G2−30 m =

5+44−30=19 m

=> R2=0.4 kg

3 R

R=R1+R2=0.0+0.4=0.4 kg

4.4.4

To determine the complete recharge
amount

To determine the complete recharge amount (kg)

Model

Length

 (a)

5~30 m

30~40 m

40~50 m

RZASG71

2.45 kg

2.8 kg

3.15 kg

RZASG100-125

2.6 kg

2.95 kg

3.3 kg

RZASG140

2.9 kg

3.25 kg

3.6 kg

(a)

Length=L1 (pair); L1+L2 (twin, triple); L1+L2+L4 (double
twin)

4.4.5

Charging refrigerant: Setup

See 

"4.3.1 Checking refrigerant piping: Setup" on page 10

.

4.4.6

To charge additional refrigerant

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

Prerequisite: 

Before charging refrigerant, make sure the refrigerant

piping is connected and checked (leak test and vacuum drying).

1

Connect  the  refrigerant  cylinder  to  both  the  service  port  of  the
gas stop valve and the service port of the liquid stop valve.

2

Charge the additional refrigerant amount.

3

Open the stop valves.

4.4.7

To activate/deactivate the vacuum mode
field setting

Description

Summary of Contents for RZASG71M2V1B

Page 1: ...Installation manual Sky Air Advance series English Installation manual Sky Air Advance series RZASG71M2V1B RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B RZASG100M7Y1B RZASG125M7Y1B RZASG140M7Y1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...difi es Richtlijnen zoals geamendeerd Directivas seg n lo enmendado Direttive come da modifica Directivas conforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f ret...

Page 4: ...astaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota T...

Page 5: ...ltera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smje...

Page 6: ...PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplo...

Page 7: ...To check the insulation resistance of the compressor 15 5 Commissioning 15 5 1 Checklist before commissioning 15 5 2 To perform a test run 16 5 3 Error codes when performing a test run 17 6 Disposal...

Page 8: ...mm 150 6 2 0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 N...

Page 9: ...ce cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knocko...

Page 10: ...at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitr...

Page 11: ...ying or recharging activate field setting vacuum mode After finishing vacuum drying or recharging deactivate field setting vacuum mode WARNING Some sections of the refrigerant circuit may be isolated...

Page 12: ...140 b Only for RZASG100 125 2 Determine the additional refrigerant amount R R1 R2 Examples Layout Additional refrigerant amount R L2 7 m 6 4 mm L3 5 m 6 4 mm L1 35 m 9 5 mm RZASG100 Case Twin standard...

Page 13: ...deactivate the vacuum mode field setting on page 12 2 Connect the refrigerant cylinder to the service port of the liquid stop valve 3 Open the liquid stop valve 4 Charge the complete refrigerant amou...

Page 14: ...connect the electrical wiring on the outdoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Make sure the electrical wiring does NOT obstruct...

Page 15: ...nsulation resistance of the compressor NOTICE If after installation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 M then the unit...

Page 16: ...lit For any other action it needs to be lit first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve A and gas stop valve B b...

Page 17: ...f the three electrical wires L4 The air inlet or air outlet is blocked U0 The stop valves are closed U2 There is a voltage imbalance There is a missing phase in case of three phase power supply units...

Page 18: ...acles walls baffle plates E Obstacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction...

Page 19: ...for See note See note Outdoor Outdoor Indoor Indoor Upper Upper Lower Lower Fan Fan ON ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Posi...

Page 20: ...Earth leakage circuit breaker 30 mA Q1E Overload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P485928 1 2017 04 Copyright 2017 Daikin 4P485928 1 0000000Y...

Reviews: