13 

English

Perform the electric wiring work in accordance with the 

• 

“electric wiring diagram label”.
Make sure to turn OFF the branch switch and overcurrent 
protective device before starting the work.
Perform grounding to the indoor unit and outdoor unit.

• 

Use only copper wires.

• 

Make sure to turn the power off before starting the electric 

• 

wiring work.
Do not turn ON any switch until the work is completed.
The outdoor unit has an inverter which generates noise and 

• 

charges the outer casing with the leakage current. The 
outdoor unit should be grounded so that the effect of the 
generated noise on other equipment can be reduced, and 
that the outer casing can be discharged.
As this unit is equipped with an inverter, installing a phase 

• 

advancing capacitor will not only reduce the power factor 
improvement factor, but may also cause the capacitor to 
overheat due to high-frequency waves.  Therefore, never 
install a phase advancing capacitor.
Never push excessive electric wires into the units.

• 

Protect electric wires with conduit tubes or vinyl tubes so 

• 

that they will not be damaged by edges of knockout holes.
Fix electric wires with clamps as accessories so that they will 

• 

not come to contact with pipes and stop valves.
(Refer to  “

7-3 Power supply wiring connection procedure

”.)

Connection example of whole system wiring

7-1 

Power

Remote 
controller 

Indoor 

unit

Ground

Power

Ground

Outdoor unit

16V

208/230V

208/230V

16V

Ground fault 
circuit interrupter

overcurrent 
protective device

Branch switch

Routing power supply wiring and transmission 

7-2 

wiring

Let the power supply wiring with a conduit pass through one of 
the knockout holes on the front or side cover, and let the 
transmission wiring with a conduit pass through another 
knockout hole.

For protection from uninsulated live parts, thread the power 

• 

supply wiring or the transmission wiring through the included 
insulating tube and secure it with the included clamp.

Insulating tube
(accessory)

Clamp
(accessory)

Power supply wiring 

or

Transmission wiring

(3in.)

Precautions when knocking out knockout holes

To punch the knockout hole, hit it with a hammer.

• 

After removing the knockout hole, it is recommended that 

• 

the edges should be painted to prevent rusting.

 CAUTION

Use conduit for both the power supply wiring and transmis-

• 

sion wiring.
Outside the unit, make sure to keep the wirings 5 inches 

• 

away.
Otherwise, the outdoor unit may be affected by electrical 
noise (external noise), and malfunction or fail.
Be sure to connect the power supply wiring to the terminal 

• 

block and secure it as described in  “7-3 Power supply wiring 
connection procedure”.
Fix the wiring between the units in accordance with 

• 

“7-4 Transmission wiring connection procedure”.
Secure the wirings with the clamps (accessory) so that do 

• 

not touch the piping.
Make sure the wirings will not be pinched by the front panel, 

• 

and close the panel fi rmly.
Route the conduit along the unit by using a elbow socket 

• 

and so on to prevent it from being stepped on.

Power supply wiring connection procedure

7-3 

 WARNING

Never connect power supply wiring to the terminal block for 

• 

remote controller wiring as this could damage the entire system.

Install a ground fault circuit interrupter.

It is obliged to install a ground fault circuit interrupter to 

• 

prevent electric shock and fi re accident.

Model

Phase and 

frequency

Voltage

Max.Overcurrent 

Protective Device

Min. Circuit 

Amps.

RZQ18PVJU
RZR18PVJU

~ 60Hz

208/230V

20A

16.5A

RZQ24PVJU
RZR24PVJU

RZQ30PVJU
RZR30PVJU

01_EN_3P281953-2A.indd   13

01_EN_3P281953-2A.indd   13

1/18/2011   9:27:23 AM

1/18/2011   9:27:23 AM

Summary of Contents for RZQ18PVJU (9)

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...e area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the...

Page 3: ...th s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping...

Page 4: ...JU RZR18PVJU RZQ24PVJU RZR24PVJU RZQ30PVJU RZR30PVJU Precaution Refrigerant R410A Power 208 230V 60Hz FAQ Wall mounted Cooling MBh 18 0 24 0 a Heating MBh RZQ only 20 0 26 0 b FCQ Ceiling mounted Cool...

Page 5: ...If strong wind whose velocity is 11 mph or more blows to the outdoor unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the...

Page 6: ...space for wiring with conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 Whe...

Page 7: ...let side is higher than the outdoor unit There is no restriction in the height of obstruction on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 L 4 o...

Page 8: ...ensional relationship between H L and A is as shown in the table below L A 0 L 1 2H 10 1 2H L H 12 When an obstruction is present also in the upward area When one outdoor unit is installed individuall...

Page 9: ...L 1 2H 10 1 2H L H 12 H L Installation is not allowed CAUTIONS ON INSTALLATION 5 Before installation confirm the strength and levelness of the foundation so that vibrations and noise are not generated...

Page 10: ...Protect the piping to prevent moisture and dusts from com ing into the piping Especially pay attention when passing the piping through a hole or connecting the end of piping to the outdoor Location W...

Page 11: ...er action such as caulking the connection area Measures to prevent invasion of small creatures and litter Block all gaps in the piping penetration areas with putty or heat insulating material arranged...

Page 12: ...refrigerant calculated by the formula below Additional charging amount Liquid piping length 0 036 Additional charging depended on type of indoor unit lb ft 0 036 A lb Indoor unit FAQ FCQ FHQ FTQ Addi...

Page 13: ...When the valve stem cannot be turned any more stop 2 turning Now the valve is open How to close the stop valve Insert a hexagon wrench into the valve stem and turn the 1 valve stem clockwise When the...

Page 14: ...smission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring or the transmission wiring through the included insulating t...

Page 15: ...ss cannot be connected to the power terminal block Slack in the electric wires may generate abnormal heat Use round pressure terminals with insulting sleeve for connection to the power terminal block...

Page 16: ...RANT PIPING WORK Piping size and heat insulation 5 Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping Check of stop valve 6 Confirm that the stop valve is open on both the liquid...

Page 17: ...ation the status under execution is indicated on the remote controller 6 After the check operation make sure to close the front panel of the outdoor unit Cautions on check operation If the air conditi...

Page 18: ...g UH The transmission wiring is not connected correctly Connect correctly the transmission wiring to the F1 and F2 TO IN D UNIT terminals on the PC board A1P in the outdoor unit When nothing is displa...

Page 19: ...al amount of refrigerant lb in the system NOTE Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separat...