10. ON SITE SETTING AND CHECK ITEMS BEFORE TEST RUN
10-1 CHECK ITEMS BEFORE THE TEST RUN
What to check
Check
column
Power supply wiring
Transmission wiring
Earth wiring
Is all wiring laid as instructed?
Is all the wiring connected? Are there no missing or reversed phases?
Is the wiring between units all in the correct order between the units?
Is the unit completely grounded?
Are the screws on the wiring attachments all thoroughly in screwed in?
Has the insulation resistance tested to at least 1 M
Ω
?
•
Use a 500V mega-tester for measuring insulation.
•
Note: Do not use the mega-tester for currents other than 230V.
Refrigerant piping
Is the piping size correct?
Is the piping insulation applied correctly?
Is the liquid and gas-side piping all insulated?
Are the stop valves for both the liquid and gas sides open completely?
Operating the unit with the valves shut will break the compressor.
Amount of refrigerant
Did you fill in the additional charging and recharging rate, and piping
length on the caution label attached to the rear side of the front panel?
Indoor unit
Is the indoor unit fully installed?
•
When the test run is started, the fan automatically begins turning.
If a decoration panel is not attached, make sure that no work is being
done on the indoor unit.
•
If you are using the wireless remote controller, do the test run after
attaching the decoration panel to the indoor unit.
01_EN_3P281953-1B.fm Page 26 Tu esday, January 25, 2011 3:35 PM
Summary of Contents for RZQ20LCVAK
Page 30: ...MEMO...
Page 31: ...FBQ20EAVAK FBQ24EAVAK FBQ36EAVAK FBQ45EAVAK FBQ48EAVAK FBQ48EAVMK...
Page 32: ......
Page 33: ...R410A SUNISO R410A R410A R407C R410A R410A...
Page 34: ...R410A M5 16 24 20 48 45 36 M4 8...
Page 35: ...BRC1E62 BRC1D61 BRC1C61 BRC4C62 BRC4C64 FBQ48EAVMK BRC4C62...
Page 36: ......
Page 37: ...A 1 A 2...
Page 38: ...M10 A 1 A 2 B D B C D 24 20 48 45 36...
Page 39: ......
Page 40: ...C RH C R410A R410A...
Page 41: ...A...
Page 42: ......
Page 43: ...BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677...
Page 44: ......
Page 45: ......
Page 46: ...ASSY...
Page 47: ...X2M...
Page 48: ...X1M X2M...
Page 49: ......
Page 50: ...36 24 20 48 45 FBQ48EAVMK...
Page 51: ...P1 P2 2 P 1 P 2 P 1 P...
Page 52: ...S M P1 P2...
Page 53: ...L H...
Page 54: ...Daikin LCD...
Page 55: ......
Page 56: ...A1 A3 A6 A8 AF AH AJ C1 C4 C6 C9 CC CJ E0 E1...
Page 58: ...U4 UF UF U5 U8 UA UC UJ...
Page 59: ......
Page 91: ...English 30 MEMO...
Page 92: ...31 English MEMO...
Page 94: ...2 1...
Page 95: ...3 1 1 1 2 3 4 5 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...
Page 96: ...4 2 1 2 48 2 2 1 1 2 1 2 3 1 3 3 71 PP 2 1...
Page 97: ...5 3 1 4 6 3 2 5 5 4 1 1 1 5 1 5...
Page 103: ...11 4 2 1 3 1 B 1 2 40 D C 2 2 1 3 1 25 3 A 4 4 A D 5 4 4 4 1 3 2...
Page 104: ...12 100 M12 6 20 6 1 6 R410A BCuP 11 8 6...
Page 105: ...13 2 6 3 6 5 6 6 6 5 6 4 6 Suniso R407C R410A R410A 755 0 1...
Page 107: ...15 10 7 11 16 10 11...
Page 108: ...16 12 13 6 4 1 2 1 2 14 13 12 16 5 13 5 27 5 22 5...
Page 109: ...17 15 15 75 C 30 20 80 C 30 C 120 13 9 11 5 14...
Page 110: ...18 1 4 3 1 1 15 9 5 39 9 32 7 13 2 12 8 15 9 75 4 61 8 19 7 19 3...
Page 111: ...19 Daikin 0 02 7 4 0 9 5 90 60 200 15 9 60 30 300...
Page 113: ...21 0 011 0 09 1 2 3 R410A 4 8 R410A RZQ 20 24 RZQ 36 45 RZ Q R 48...
Page 114: ...22 9 230 500...
Page 115: ...V L N Y...
Page 116: ...24 M4 1 8 1 2 M5 3 0 2 0 M4 1 9 1 4 M5 2 9 2 4...
Page 117: ...Y V RZ Q R V Y 20 24 36 45 45 48 MCA A RZR48MUYMK...
Page 118: ......
Page 119: ...27 11 1 01 2 88 3 4 10 03 04 05 6 10 8 10 8 8 01 02 26 16 0 1...
Page 122: ...30...
Page 123: ......