ESIE04-01
Indoor Unit Functional Concept
Part 2 – Functional Description
2–27
3
2
4
5
1
2.3
Drain Pump Control
Purpose
Control the water draining from the drain pan.
Starting conditions
The drain pump control starts the drain pump motor when one of the following conditions is fulfilled:
P
Cooling operation is activated
P
Abnormal high water level is detected in the drain pan
Normal control
In normal control, the drain pump is turned ON at compressor starting and turned OFF 5 minutes after
the compressor has stopped (residual operation).
Float switch
activation during
thermostat OFF
When an abnormal drain level is detected in the drain pan, the float switch opens:
1
The thermostat stays forced OFF.
2
The drain pump starts to operate for minimum 10 minutes (even if abnormality is solved within the
10 minutes).
3
If the float switch closes again within 80 seconds, cooling operation can restart within the 10
minutes recovery period.
Drain pump
ON
OFF
Compressor
ON
OFF
5 min
Water level
abnormality
Abnormal
Normal
5 min
5 min
1 min 20
5 s
Normal
Float switch
Compressor
Drain pump
Error processing
OFF
OFF
ON
ON
RZQ - Final.book Page 27 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...