ESIE04-01
Introduction
vii
3
4
5
1.3.4
Service Tools
R410A is used under higher working pressure, compared to previous refrigerants (R22,R407C).
Furthermore, the refrigerating machine oil has been changed from Suniso oil to Ether oil, and if oil
mixing is occurred, sludge results in the refrigerants and causes other problems. Therefore, gauge
manifolds and charge hoses that are used with a previous refrigerant (R22,R407C) can not be used
for products that use new refrigerants.
Be sure to use dedicated tools and devices.
P
Tool compatibility
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of charge
hose.
Tool
Compatibility
Reasons for change
HFC
HCFC
R410A
R407C
R22
Gauge manifold
Charge hose
X
P
Do not use the same tools for R22
and R410A.
P
Thread specification differs for
R410A and R407C.
Charging cylinder
X
O
P
Weighting instrument used for
HFCs.
Gas detector
O
X
P
The same tool can be used for
HFCs.
Vacuum pump
(pump with reverse flow
preventive function)
O
P
To use existing pump for HFCs,
vacuum pump adaptor must be
installed.
Weighting instrument
O
Charge mouthpiece
X
P
Seal material is different between
R22 and HFCs.
P
Thread specification is different
between R410A and others.
Flaring tool (Clutch
type)
O
P
For R410A, flare gauge is
necessary.
Torque wrench
O
P
Torque-up for 1/2 and 5/8
Pipe cutter
O
Pipe expander
O
Pipe bender
O
Pipe assembling oil
X
P
Due to refrigerating machine oil
change. (No Suniso oil can be used.)
Refrigerant recovery
device
Check your recovery device.
Refrigerant piping
See the chart below.
P
Only
φ
19.1 is changed to 1/2H
material while the previous material is
"O".
RZQ - Final.book Page vii Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...