Outdoor Unit Functional Concept
Part 2 – Functional Description
2–47
3
2
4
5
1
3.3.5
Discharge Pipe Temperature Control
Outline
The compressor operating frequency will be controlled in order to avoid abnormal high compressor
temperatures (see also expansion valve control).
Flow chart
Parameters
Td = Discharge pipe temperature
Normal operation
OR
OR
&
OR
OR
Td > B°C
Compressor upper limit frequency
–1 step/20 sec
Compressor upper limit frequency
+1 step/1 min
Compressor upper limit frequency
79 Hz (RZQ71)
62 Hz (RZQ100 & 125
Compressor stop
Malfunction stop (F3 indication)
10 times or less stopping in 200 minutes
Td
≤
B°C
•
Td
<
A°C
• Upper limit frequency
= Maximum frequency
• Td
≤
B°C
• 5 min elapsed
• Td
<
A°C
• Td > C°C
• 300 sec
• Td
≥
E°C continues
for G minutes
• Td
≥
F°C
Stopped 11 times
in 200 minutes
• &
• Td
>
D°C
RZQ71B
RZQ100 & 125B
A°C
100°C
100°C
B°C
105°C
105°C
C°C
110°C
110°C
D°C
120°C
120°C
E°C
110°C
115°C
F°C
125°C
135°C
Gmin
15min
10min
RZQ - Final.book Page 47 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...