Outdoor Unit Functional Concept
ESIE04-01
2–48
Part 2 – Functional Description
3
1
2
4
5
3.3.6
Suction Pipe Superheat Protection Control (Heating Mode)
Outline
In case the suction superheat value in heating mode is too high, the oil return to the compressor will
be insufficient. In order to avoid that the compressor oil will be accumulated in the outdoor unit heat
exchanger, the upper limit frequency will be decreased.
Flow chart
Normal operation
Lowering upper limit
frequency for 1-step
every 20 seconds
Raising upper limit
frequency for 1-step
every 20 seconds
• Suction SH > 12°C
• Suction SH > 10°C
• EV opening degree = 480pls
• Suction SH > 12°C
• Suction SH > 10°C
• EV opening degree = 480pls
• Suction SH < 10°C
• EV opening degree < 450pls
• Suction SH < 8°C
• Suction SH < 6°C
• Suction SH < 6°C
• Upper limit frequency = Maximum frequency
• Suction SH < 8°C
• Suction SH < 10°C
• EV opening degree < 450 pls
OR
OR
OR
OR
&
&
&
• &
•OR
• &
RZQ - Final.book Page 48 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...