Outdoor Unit Functional Concept
ESIE04-01
2–54
Part 2 – Functional Description
3
1
2
4
5
3.3.11 Oil Recovery Operation
Outline
When the compressor operates for a certain period of time at low frequency, the oil level in the
compressor may become low due to incomplete oil recovery.To prevent damage to the compressor
and in worst case avoid compressor lock, an oil recovery operation will be conducted.
Details
During the oil recovery operation, the operation frequency of the compressor will be increased for a
time period of 10 minutes.
Example
Trigger conditions for 71-class:
P
In cooling : Compressor frequency = 62 Hz for 10 minutes continuously.
P
In heating : Compressor frequency = 109 Hz for 10 minutes continuously.
When the above conditions are fulfilled, a calculation of the oil discharge amount will be executed
according to the below formula:
Oil discharge amount = inverter frequency (Hz) x D x
∆
time
(D = constant value depending on outdoor unit type).
When the result of the above calculation is lower than a reference value programmed in the unit's
memory, the oil recovery operation will be started:
The compressor will operate at a frequency above 62 Hz in cooling and 109 Hz in heating for 10
minutes continuously.
RZQ - Final.book Page 54 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...