ESIE04-01
Troubleshooting
Part 3 – Troubleshooting
3–13
3
3
4
5
1
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Normal. Unit is in 3-min
standby mode
Contact power company
Check compressor
Replace power cable
Expansion valve
malfunction
Four-way valve malfunction
Check compressor
Turn the operation switch ON
and OFF, then wait at ON
side.
After vacuum drying, charge
correct amount of refrigerant.
Then, start operation again.
NO
YES
YES
YES
Malfunction of compressor
YES
YES
Is the
discharge side of
compressor hot after unit
stop?
Is there any
temperature difference
between inlet and outlet
of expansion
valve?
Is
there any
temperature difference
between suction side and
discharge side of
four-way
valve?
Power
supply voltage is within
±10 % of specified
voltage.
Is the
size of power cable
through total length
correct?
Does the unit
start operation after
3 minutes?
NO
NO
NO
NO
YES
[Electric system]
[Refrigerant circuit]
Not so hot
NO
(S1993)
Check on the cause why
overcurrent relay (for
compressor) or compressor
protection thermostat acted.
RZQ - Final.book Page 13 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...