Troubleshooting
ESIE04-01
3–18
Part 3 – Troubleshooting
3
1
3
4
5
1.3.7
Equipment discharges white mist
Applicable Model
All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Cause
P
Humid installation site
P
Installation site is dirty and with dense oil mists.
P
Soiled heat exchanger
P
Clogged air filter
P
Malfunction of fan motor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Normal
Remove the source of humid
condition.
Cleaning of heat exchanger
is necessary.
Remove the source of oil
mist or dust.
Cleaning of air filter
Check fan motor
(Refer error code “A6”)
Normal
(Fog is generated due to
defrosting operation)
Is white fog coming
out from the unit?
Is the heat
exchanger of indoor
unit soiled?
Is the site
dusty or with dense
oil mist?
NO
NO
NO
Is the
airflow rate too small?
NO
NO
YES
YES
YES
YES
Is the room
temperature higher than
set value in cooling
operation?
YES
Continue unit operation.
It may be necessary to
remove the source of humid
condition.
Dust or oil mists should be
removed.
Possible causes as follows
∗
Clogged air filter
∗
Malfunction of fan motor
Did the trouble generate on
switching to heating mode
after complete of defrosting
during heating?
(S1996)
RZQ - Final.book Page 18 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...