Error Codes: Outdoor Units
ESIE04-01
3–64
Part 3 – Troubleshooting
3
1
3
4
5
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Problem could be caused
by external factor (noise, etc.)
other than malfunction.
Normal reset?
Is
coil resistance
of electronic expansion
valve normal?
(40 to 50
Ω
)
(
*
)
YES
Replace the electronic
expansion valve coil.
Replace the outdoor unit
PC board (A1P).
NO
Connect correctly.
Is the
electronic expansion
valve coil connected
to outdoor unit
PC board?
NO
NO
Turn the power supply
off once and back on.
NO
YES
YES
Replace the motorized
valve coil.
With remote
controller ON, doesn’t
the unit operate and
is “E9” displayed?
NO
Replace the main unit of
solenoid valve (Y2S).
Is there
difference in
temperature before and
after solenoid valve
(Y2S) during
operation?
YES
*
Measure the resistance between each pin of
connector and make sure that the resistance
ranges between 40 and 50
Ω
.
1
2
3
4
5
Measurement point
1—5
2—5
3—5
4—5
(S2585)
RZQ - Final.book Page 64 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...