Error Codes: System Malfunctions
ESIE04-01
3–92
Part 3 – Troubleshooting
3
1
3
4
5
4.3
Malfunction of Transmission between Indoor Unit and Remote Controller (
U5
)
Error code
U5
Error generation
The error is generated when the microprocessor detects that the transmission between the indoor unit
and the remote controller is not normal over a certain amount of time.
Causes
The possible causes are:
P
Malfunctioning remote controller
P
Malfunctioning indoor PCB
P
Outside cause (noise...)
P
Connection of two master remote controllers (when using two remote controllers).
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Set one of the
remote controllers
to SUB, turn off
the power supply
temporarily, then
restart operation.
Indoor unit PCB
replacement.
Malfunction could
be produced by
noise. Check the
surrounding area
and restart
operation.
Change to
double-core
independent
cable.
Failure of remote
controller PCB or
replacement of
defective indoor
unit PCB.
All indoor
unit PCB
microcomputer
normal monitors
flashing
Using
multicore
transmission wiring
between indoor unit
and remote
controller
Control by 2 remote
controllers
NO
YES
YES
YES
YES
Resets
normally when
power supply is turned
off temporarily.
NO
SS1 of both
remote controllers is
set to MAIN.
YES
NO
NO
RZQ - Final.book Page 92 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...