ESIE04-01
Error Codes: System Malfunctions
Part 3 – Troubleshooting
3–95
3
3
4
5
1
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is there
220-240 VAC
between No.1 and
No.3 of X2M
(indoor Unit)?
Is the
power supply
PCB correctly
connected?
YES
YES
YES
Is the
indoor-indoor
and indoor-outdoor
jumper correctly
connected?
Is the
indoor-indoor
and indoor-outdoor
jumper correctly
connected?
NO
NO
NO
NO
Is
the outdoor unit
used for Twin
system?
Is
the remote
controller connected
to more than
one indoor
unit?
NO
YES
Are the
microcomputer
normal montiors
(HAP) of all indoor unit
PCB
flashing?
YES
Are the
transmission
normal montiors
(HBP) of all indoor unit
PCB
flashing?
NO
Is the
setting of
Pair/Twin/Triple
set
correctly?
YES
NO
YES
NO
YES
Operating normally?
YES
YES
NO
NO
Turn the power off once, then
back on, and restart operation.
Connect the remote controller
correctly.
Check setting "No. of Connected
Twin System Indoor Units" of indoor
unit.
Set correctly.
Connect correctly.
Connect correctly.
Replace the transformer.
Wiring could be incorrect, recheck.
Connect correctly.
Indoor unit PCB replacement.
Operates normally.
RZQ - Final.book Page 95 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...