Additional Checks for Troubleshooting
ESIE04-01
3–98
Part 3 – Troubleshooting
3
1
3
4
5
5.2
Indoor Unit: Checking the Fan Motor Hall IC
Applicable units
Units using phase cut controlled fan motor with feedback signal.
Checking
To check the indoor unit fan motor hall IC, proceed as follows:
Step
Action
1
Make sure connector S7 on PCB 1 is properly connected.
2
Make sure the power is ON and that there is no operation.
3
Measure the voltage between pin 1 and 3 of S7.
4
Turn the fan one rotation with your hand and measure the generated pulses.
5
Proceed as follows:
If...
Then...
The measured voltage between pin 1 and 3 does
not equal 5 V
Replace the PCB 1.
The generated pulses do not equal 3 pulses
between pin 2 and 3
Replace the fan motor.
The measured voltage does not equal 5 V and
the generated pulses do not equal 3 pulses
between pin 2 and 3
Replace the PCB 1.
RZQ - Final.book Page 98 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...