Outdoor Unit: Checking the Expansion Valve
Checking
To check the electronic expansion valve, proceed as follows:
Step
Action
1
Check if the expansion valve connector is correctly inserted in the X12A of A1P.
2
Compare the expansion valve unit with the number of the connector to make sure it is cor-
rectly connected.
3
Switch the power OFF.
4
Switch the power ON to check whether the expansion valve is producing a clicking sound.
5
Check the coil current: Open circuit < normal < short circuit
6
Check the clicking sound again.
If...
Then...
The expansion valve has no
clicking sound
Disconnect the valve connector without the
clicking sound and proceed to step 5.
The table below contains the reference resistance values.
—
White
Grey
Black
Yellow
Red
Orange
White
—
45
ø
45
ø
Grey
—
45
ø
45
ø
Black
45
ø
—
90
ø
Yellow
45
ø
—
90
ø
Red
45
ø
90
ø
—
Orange
45
ø
90
ø
—
If...
Then...
There is a clicking sound
The expansion valve works properly.
There is no clicking sound
Replace the expansion valve unit.
There is still no clicking sound
Replace outdoor PCB A1P.
RZQ - Final.book Page 101 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...