Additional Checks for Troubleshooting
ESIE04-01
3–110
Part 3 – Troubleshooting
3
1
3
4
5
5.11.5 Outdoor unit: Check for Power Transistor
Judgment according to the continuity check by using an analog tester:
(1) Do not touch the charged area (high voltage) for 10 minutes after turning the power supply off.
(2) If you must touch such an area, make sure that the power supply voltage of power transistor is 50
V or less.
(3) Before measuring the continuity, disconnect the connection between compressor and power
transistor.
(4) Measure the continuity in the following procedure.
[Judgment] Normal if the continuity check results in the following.
Power transistor
(on inverter PC
board)
*
If there is continuity, the resistance should be the same as each phase.
*
If a digital tester is used for the measurement of continuity,
∞
and continuity may be reversed.
P — U
Continuity
P — V Continuity
P — W Continuity
U — P
∞
V — P
∞
W — P
∞
*
U — P
∞
V — P
∞
W — P
∞
P — U
Continuity
P — V Continuity
P — W Continuity
*
(S2678)
RZQ - Final.book Page 110 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...