Pre-Test Run Checks
ESIE04-01
4–8
Part 4 – Commissioning and Test Run
3
1
4
5
Multiple settings
A/b
When an outside control (central remote controller...) controls an indoor unit, sometimes the indoor
unit does not respond to ON/OFF and temperature settings commands from this controller.
5
Press the TEST button to quit the field set mode and return to the normal display.
Step
Action
UP
FAN
RESERVE CANCEL
TIMER
DOWN
TEMP
TIME
ON / OFF
MODE
SWING
/TEST
˚C
TEST
Remote controller
Indoor unit
Setting
Remote controller
display
Control of other air condi-
tioners and units
No other control
A: Standard
All items are displayed.
Commands other than ON/OFF
and temperature setting
accepted. (1 long beep or
3 short beeps emitted)
b: Multi Sys-
tem
Only one item is dis-
played. This item is
only shown for a few
seconds.
All commands accepted (2 short beeps)
RZQ - Final.book Page 8 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...