Field settings
ESIE04-01
4–16
Part 4 – Commissioning and Test Run
3
1
4
5
2.7
Setting the Filter Counter
Mode No. 10 or 20
First code No. 0
When the filter counter indication time is set to ON, set the second code No., according to the table
below
Fan speed OFF
when
thermostat OFF
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting to
“Fan OFF”. This setting is used as a countermeasure against odour, for example for barber shops and
restaurants.
Fan speed
changeover when
thermostat OFF
You can switch the fan speed to the set fan speed when the heating thermostat is OFF. This setting is
called “Set Fan Speed”.
Air flow direction
setting
Set the air flow direction of the indoor units as given in the table below. This setting is needed when
the optional air outlet blocking pad has been installed. The “Second code No” is factory set to “01”.
Unit
Mode No.
First code No.
Second code No.
Contamination
01
02
light
heavy
FCQ
10 or 20
0
±2500 hrs
±1250 hrs
FFQ
±2500 hrs
±1250 hrs
FHQ
±2500 hrs
±1250 hrs
FUQ
±2500 hrs
±1250 hrs
FAQ
±200 hrs
±100 hrs
FBQ
±2500 hrs
±1250 hrs
FDQ
±2500 hrs
±1250 hrs
Mode No.
First code No.
Second code No.
Setting
11 or 21
2
01
—
02
Fan OFF
Mode No.
First code No.
Second code No.
Setting
12 or 22
3
01
LL fan speed
02
Set fan speed
Mode No
First code No
Second code No
Setting
13 or 23
1
01
F: four-direction air flow
02
T: three-direction air flow
03
W: two direction air flow
RZQ - Final.book Page 16 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...