Field settings
ESIE04-01
4–34
Part 4 – Commissioning and Test Run
3
1
4
5
Graph 3
Target evaporating temperature control when "low humidity appli freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Change thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the rise
of temperature after thermostat OFF, the thermostat control will be changed when using field settings
16(26)-2-03 & 16(26)-2-04.
Thermostat ON
P
∆
Trs
≥
0.5 °C (No change from standard setting)
Thermostat OFF
P
∆
Trs
≤
-2.0 °C for 5 minutes continuously.
P
∆
Trs
≤
4.5 °C
Remote controller setting temp.
Te target limitted
≤
20°C
(to protect the comp.)
Te (by LP sensor) target acceptable area
P
Indoor temp.
>
setting
→
Te target down
P
Indoor temp.
<
setting
→
Te target up
Te target limitted
≥
2°C
(not to freeze)
Freeze protection
(40min. integrated coil temp.
≤
-1°C)
Te target acceptable area
Te target
(°C)
Indoor Temp
(°C DB)
RZQ - Final.book Page 34 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...