Test Run and Operation Data
ESIE04-01
4–40
Part 4 – Commissioning and Test Run
3
1
4
5
Correlation of
Air-Conditioner’s
Operation Status
and Pressure /
Running Current
What happens in comparison to normal values is summarized in the table below.
(Measured from 15 ~ 20 minutes or more after operation starts.)
When Cooling
When Heating
Notes:
P
∗
1. Water in the refrigerant freezes inside the capillary tube or expansion valve, and is basically
the same phenomenon as pump down.
P
∗
2. Dirt in the refrigerant clogs filters inside the piping, and is basically the same phenomenon as
pump down.
P
∗
3. Pressure differential between high and low pressure becomes low.
Air-Conditioner Status
Low Pressure
High Pressure
Running Current
Air Filter Fouling
Lower
Lower
Lower
Short Circuit of Indoor Unit
Inlet/Outlet Air
Lower
Lower
Lower
Outdoor Unit Fin Fouling
Higher
Higher
Higher
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Higher
Higher
Higher
Air Mixed in Refrigerant
Higher
Higher
Higher
Water Mixed in Refrigerant
∗
1 Lower
Lower
Lower
Dirt Mixed in Refrigerant
∗
2 Lower
Lower
Lower
Lack of Refrigerant (Gas)
Lower
Lower
Lower
Unsatisfactory Compression
∗
3 Higher
Lower
Lower
Air-Conditioner Status
Low Pressure
High Pressure
Running Current
Air Filter Fouling
Higher
Higher
Higher
Short Circuit of Indoor Unit
Inlet/Outlet Air
Higher
Higher
Higher
Outdoor Unit Fin Fouling
Lower
Lower
Lower
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Lower
Lower
Lower
Air Mixed in Refrigerant
Higher
Higher
Higher
Water Mixed in Refrigerant
∗
1 Lower
Lower
Lower
Dirt Mixed in Refrigerant
∗
2 Lower
Lower
Lower
Lack of Refrigerant (Gas)
Lower
Lower
Lower
Unsatisfactory Compression
∗
3 Higher
Lower
Lower
RZQ - Final.book Page 40 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...