ESIE04-01
Disassembly and Maintenance: Outdoor Units
Part 5 – Disassembly and Maintenance
5–9
3
5
1
5
1.2.4
Removal of PC Board Ass'y (1)
Warning
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure
Step
Procedure
Points
P
Remove the front and top
panels in accordance with the
Removal Procedure for
Outside Panel
1
Remove the PC board (for
control use)
1
Disconnect all
connectors.
P
Disconnect the relay
connector from the
lead wire of the
compressor.
(Only on
RZQ71B7V3B)
P
Remove the lead
wire from the terminal
cover of the
compressor.
P
Remove the lead
wire from the terminal
of the high pressure
switch.
(Only on
RZQ71B7V3B)
P
Disconnect the
respective
connectors from the
following parts on the
PC board.
P
Each thermistor
P
Low pressure
sensor
P
Coil of four way
valve
P
Coil of solenoid
valve (Only on
RZQ100-125B7V
3B)
P
Coil of motorized
valve
Fixing screw of PC board ass'y
(for control use)
RZQ - Final.book Page 9 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...