Specifications
ESIE04-01
1–44
Part 1 – System Outline
3
11
4
5
3.2
RZQ71, RZQ100 and RZQ125
Technical
specifications
The table below contains the technical specifications.
Specification
RZQ71B7V3B
RZQ100B7V3B
RZQ125B7V3B
Compressor
Model
2YC63BXD
JT100FCVD
Type
Hermetically sealed swing
compressor
Hermetically sealed scroll compressor
Crankcase heater
33 W
Motor output
1800 W
2200 W
Speed
Heat exchanger
Length
866 mm
857 mm
No. of rows
2
Fin pitch
2.00 mm
No. of passes
5
10
Face area
0.648 m²
1.131 m²
No. of stages
34
60
Tube type
Hi-XSS(8)
Fin type
Non-symmetric waffle louvre
Fin treatment
Anti-corrosion treatment (PE)
Empty tubeplate hole
0
Fan
Type
Propeller
Discharge direction
Horizontal
No. of fans
1
2
Nominal air flow rate (230 V) cooling
54.50 m³/min
103.00 m³/min
99.00 m³/min
Nominal air flow rate (230 V) heating
48.10 m³/min
101.00 m³/min
100.00 m³/min
Fan motor model
KFD-325-70-8A
Fan speed (nominal at 230 V) No. of steps
8
Fan speed (nominal at 230 V) cooling
813 rpm
802 rpm
772 rpm
Fan speed (nominal at 230 V) heating
721 rpm
787 rpm
779 rpm
Drive
direct drive
Refrigerant circuit
Type
R410A
Charge
3.20 kg
4.30 kg
Control
Expansion valve (electronic type)
No. of circuits
1
Safety and functional devices
High pressure switch
Fan motor thermal protector
Fuse
Heat insulation
Both liquid and gas pipe
Weight
Machine weight
61 kg
106 kg
Gross weight
65 kg
111 kg
RZQ - Final.book Page 44 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...